Table 13: Status of RGU-100B�
Possible statuses of RGU-100B
Value
Description
0
Device in startup process
1
Device idle
2
Device tripped due to activation of the
TRIP
input
7�3�2�- CHANNEL VARIABLES
Function 0x04
: reading of registers, is used for these variables
Table 14: Modbus Memory Map: Channel variables�
Configuration variable
Format
Address
Units/Format
WGB
model
String
FA0-FA1
-
Serial no. of
WGB
String
FA2...FA8
-
Firmware version (part 1)
Unit [16]
FA9
-
Firmware version (part 2)
Unit [16]
FAA
-
Firmware version revision
Unit [16]
FAB
-
WGB
status
Unit [16]
FAC
0��� 6
(see
)
WGB
channel
Unit [16]
FAD
1:
channel 1
Programmed trip curve or delay
Unit [16]
FAE
ms
Programmed trip current
Unit [16]
FAF
mA
Instant total leakage current
Unit [16]
FB0
mA
Instant alternating leakage current
Unit [16]
FB1
mA
Instant direct leakage current
Unit [16]
FB2
mA
Total leakage current that tripped the relay
Unit [16]
FB3
mA
Alternating leakage current that tripped the relay
Unit [16]
FB4
mA
Direct leakage current that tripped the relay
Unit [16]
FB5
mA
Programmed prealarm current
Unit [16]
FB6
%
Prealarm Operation
Unit [16]
FB7
0:
Deactivated
1:
Activated with deactivated latch
2:
Activated with activated latch
Possible statuses of
WGB
Table 15: WGB statuses�
Possible statuses of WGB
Value
Description
0
WGB
in startup process
1
WGB
in idle status
2
WGB
tripped due to detected leakage current
3
WGB
tripped due to TEST with Test error result
4
WGB
tripped due to TEST with Test successful result
5
WGB
tripped due to communications
6
WGB
tripped due to
TRIP input
Function 0x02
is used for these variables.
Summary of Contents for RGU-100B
Page 1: ...INSTRUCTION MANUAL Protection and monitoring relay RGU 100B M256B01 03 20A...
Page 2: ...2 RGU 100B Instruction Manual...
Page 47: ...47 Instruction Manual RGU 100B 11 CE CERTIFICATE...
Page 48: ...48 RGU 100B Instruction Manual...
Page 49: ...49 Instruction Manual RGU 100B...
Page 53: ...53 Instruction Manual RGU 100B...