Table 16:Modbus Memory Map: Channel status�
Parameter
Format
Address
Value
Internal error detected in the
WGB
bool
0000
0:
Not detected
1:
Detected
Prealarm activated
bool
0001
0:
Deactivated
1:
Activated
Channel tripped
bool
0002
0:
Not tripped
1:
Tripped
Channel tripped due to leakage current
bool
0003
Channel tripped due to error in the
WGB
bool
0004
Channel tripped due to test
bool
0005
Channel tripped due to
TRIP
input
bool
0006
Channel tripped due to communications
bool
0007
WGB
not connected
bool
0008
0:
Not detected
1:
Detected
WGB
does not respond to requests
bool
0009
7�3�3�- TRIPPING DUE TO TEST OR COMMUNICATIONS
The following functions are used for these variables:
0x01
and
0x05
.
Table 17: Modbus Memory Map: Configuration of the trip and prealarm�
Configuration of the Trip and Prealarm
Configuration variable
Format
Address
Valid data range
Default value
Tripping due to
TEST
of channel
bool
07D0
FF00:
Activate Test of channel
0000
: Finish TEST
0000
Tripping due to Communications
of channel
bool
07D1
FF00:
Tripping of channel
0000
: Channel reset
0000
7�3�4�- EVENTS
The following steps must be taken to read the events:
1�-
Read the
No. of events in the channel
to consult.
2�-
Write the channel number to consult in
Channel selection
: 1.
3�-
Write the event number to consult in
Event selection
.
4�-
Read the 8
Event
registers simultaneously to consult the event's details.
Table 18: Modbus Memory Map: Events�
Parameter
Format
Address
Function
Value
No. of events in channel
Unit [16]
13BA
0x04
0... 10
Channel selection
Unit [16]
1388
0x03
0x10
1
Event selection
Unit [16]
1389
1... 10
Summary of Contents for RGU-100B
Page 1: ...INSTRUCTION MANUAL Protection and monitoring relay RGU 100B M256B01 03 20A...
Page 2: ...2 RGU 100B Instruction Manual...
Page 47: ...47 Instruction Manual RGU 100B 11 CE CERTIFICATE...
Page 48: ...48 RGU 100B Instruction Manual...
Page 49: ...49 Instruction Manual RGU 100B...
Page 53: ...53 Instruction Manual RGU 100B...