30
RGU-10A
Instruction Manual
7�2�1 - POLARITY
The polarity of the trip relay is configured in this section.
Press the key
to enter edit mode, the programming value flashes.
Use the keys
and
to skip through the different options.
Configuration values
Table 15:Configuration values: Polarity�
Polarity
Possible
values
YES
,
The trip relay works with positive polarity. The
+
icon is shown
on the display.
NO
,
the trip relay works with standard polarity.
Hold down the key
for > 3s to validate the data and exit edit mode.
To skip to the next programming point, press once the key
.
7�2�2 - TRIP CURRENT LIMIT
In this section, the trip current limit is set, which can be programmed as a direct setting on the device
(see
Press the key
to enter edit mode, the programming value flashes.
Use the keys
and
to skip through the different options.
Configuration values
Table 16:Configuration values: Trip current limit�
Trip current limit
Possible values
3 A
30 A
Hold down the key
for > 3s to validate the data and exit edit mode.
To jump to the home screen of the trip relay menu, press the key
for > 3s.
Summary of Contents for RGU-10A
Page 1: ...INSTRUCTION MANUAL Protection and monitoring relay RGU 10A M359B01 03 22A...
Page 2: ...2 RGU 10A Instruction Manual...
Page 38: ...38 RGU 10A Instruction Manual 11 EU DECLARATION OF CONFORMITY...
Page 39: ...39 Instruction Manual RGU 10A...
Page 40: ...40 RGU 10A Instruction Manual...
Page 43: ...43 Instruction Manual RGU 10A...