Cisco Catalyst 4900M Switch Installation Guide

78-18350-02

Chapter 1      Troubleshooting the Installation

  Troubleshooting the Power Supply

Troubleshooting the Power Supply

To help isolate a power subsystem problem, perform the following steps:

Step 1

Verify that the power supply is plugged in and that the on/off switch is set to ON (if the power supply is 
an AC supply).

Step 2

Look at the power supply LED (PS1 or PS2). If the LED is off or if the LED is red, unplug the power 
cord, and then plug the power cord in. Be sure the on/off switch is OFF before removing the power cord 
from the power supply.

Step 3

If the LED remains off, there might be a problem with the AC or DC source or the power cable. 

Step 4

Connect the power cord to another power source if one is available.

Step 5

If the LED then lights, the problem is the first power source.

Step 6

If the LED fails to light after you connect the power supply to a new power source, replace the power 
cord.

Step 7

If the LED still fails to light when the switch is connected to a different power source with a new power 
cord, the power supply is probably faulty.

If you are unable to resolve the problem, contact a customer service representative for instructions.

Contacting Customer Service

If you are unable to solve a startup problem after using the troubleshooting suggestions in this chapter, 
contact a customer service representative for assistance and further instructions. Before you call, have 
the following information ready to help your service provider assist you as quickly as possible:

Date you received the switch

Chassis serial number (located on a label on the right of the rear of the chassis, see 

Figure 1-1

)

Type of software and release number

Maintenance agreement or warranty information

Brief description of the problem

Brief explanation of the steps you have already taken to isolate and resolve the problem

Summary of Contents for 4900M - Catalyst Switch

Page 1: ...tions above the maximum acceptable level rarely occur at initial startup environmental monitoring functions are included because they also monitor DC line voltages Note For configuration questions or problems refer to the software configuration guide or the command reference publication to configure or enable the interfaces Getting Started When the initial system boot is complete verify the follow...

Page 2: ...t is operating If the FAN LED is orange and you determine that the fan assembly is not operating you should immediately contact a customer service representative There are no installation adjustments that you can make if the fan assembly does not function properly at the initial startup Identifying Startup Problems When you connect the power cords to the Catalyst 4900M switch follow these steps St...

Page 3: ...ngs LED Meaning INPUT OK AC This LED should turn green immediately when power is applied to the supply and the power switch is set to ON Green AC input voltage is greater than 80 5 VAC 4 5 VAC Red In a dual power supply configuration alternate unit powered the AC input is less than 73 VAC 3 VAC or the power supply is turned off Off In a single supply configuration signals that AC input voltage is ...

Page 4: ...urce Step 6 If the LED fails to light after you connect the power supply to a new power source replace the power cord Step 7 If the LED still fails to light when the switch is connected to a different power source with a new power cord the power supply is probably faulty If you are unable to resolve the problem contact a customer service representative for instructions Contacting Customer Service ...

Page 5: ...1 5 Cisco Catalyst 4900M Switch Installation Guide 78 18350 02 Chapter 1 Troubleshooting the Installation Contacting Customer Service Figure 1 1 Serial Number Location 202519 SN XXXNNNNXXXX ...

Page 6: ...1 6 Cisco Catalyst 4900M Switch Installation Guide 78 18350 02 Chapter 1 Troubleshooting the Installation Contacting Customer Service ...

Reviews: