Cisco 6100 Thermal Upgrade Kit Installation Procedures
78-10158-01
General Safety Precautions
Warning
To prevent bodily injury when mounting or servicing this unit in a rack, you must take
special precautions to ensure that the system remains stable. The following guidelines
are provided to ensure your safety:
- This unit should be mounted at the bottom of the rack if it is the only unit in the rack.
- When mounting this unit in a partially filled rack, load the rack from the bottom to the
top with the heaviest component at the bottom of the rack.
- If the rack is provided with stabilizing devices, install the stabilizers before mounting
or servicing the unit in the rack.
Warning
Use copper conductors only.
Warning
A readily accessible two-poled disconnect device must be incorporated in the
fixed wiring.
Warning
Do not reach into a vacant slot or chassis while you install or remove a module or a fan.
Exposed circuitry could constitute an energy hazard.
Warning
An exposed wire lead from a DC-input power source can conduct harmful levels of
electricity. Be sure that no exposed portion of the DC-input power source wire extends
from the terminal block plug.
Warning
Blank faceplates and cover panels serve three important functions: they prevent
exposure to hazardous voltages and currents inside the chassis; they contain
electromagnetic interference (EMI) that might disrupt other equipment; and they direct
the flow of cooling air through the chassis. Do not operate the system unless all cards,
faceplates, front covers, and rear covers are in place.
Warning
When installing the unit, the ground connection must always be made first and
disconnected last.
Warning
This equipment is intended to be grounded. Ensure that the host is connected to earth
ground during normal use.
Warning
Incorrect connection of this or connected equipment to a general purpose outlet could
result in a hazardous situation.