There are two sets of grounding terminals located at the lower-rear of the chassis. The following figure and
the table that follows show the location of these terminals and provide specifications for the appropriate lug
and cable size.
Figure 25: Chassis Ground Terminals
Table 25: Terminal and Cable specifications
Description
Item
Ground Terminal:
2-hole lug (0.186-inch posts, spaced 0.630-inch on center).
The method of connection is: chassis - lug - flat washer - nut (3/8-inch). The nut(s) must be torqued
to 50 in-lb (5.65 N-m).
1
Ground Cable:
Cable length: Not more than 70 feet (21.336 meters) one way.
Cable size: 6 AWG (minimum), stranded copper.
2
ASR 5000 Installation Guide
61
Chassis Installation
Grounding the Chassis