Grounding the Chassis
The chassis must be properly grounded prior to installing any chassis components or cards. The chassis and
the equipment rack/cabinet must be connected to the same ground point.
Failure to properly ground the chassis could result in personal injury and/or damage to the chassis and its
components.
Caution
There are two sets of grounding terminals located at the lower-rear of the chassis. Figure 4-8 shows the location
of these terminals and provides specifications for the appropriate lug and cable size.
Ground Cabling
The ASR 5500 is suitable for installation as part of the Common Bonding Network (CBN) in a network
telecommunications facility. It is not intended for installation in an Isolated Bonding Network (IBN).
Important
A 2-hole lug (Panduit LCD4-14A-L) is supplied for grounding the chassis. The lug must be crimped to the
end of a ground cable using Panduit crimp tool part number CT-720-1 (die color: gray, P29). The wire strip
length is 7/8-inch (22 mm),
The minimum, recommended stranded cable size is 4 AWG. the cable length to the site ground point should
not exceed 70 feet (21 m) one way.
The method of connection is: chassis -> lug -> flat washer -> nut (7/16-inch).
ASR 5500 Installation Guide
43
Chassis Installation
Grounding the Chassis
Summary of Contents for ASR 5500
Page 12: ...ASR 5500 Installation Guide xii Contents ...
Page 16: ...ASR 5500 Installation Guide xvi About this Guide Contacting Customer Support ...
Page 40: ...ASR 5500 Installation Guide 24 Technical Specifications Chassis Grounding ...
Page 74: ...ASR 5500 Installation Guide 58 Card Installation Save Shipping Cartons ...
Page 88: ...ASR 5500 Installation Guide 72 MIO Port Cabling Cleaning Fiber Optic Connectors ...
Page 112: ...ASR 5500 Installation Guide 96 System Power up show leds Command ...
Page 130: ...ASR 5500 Installation Guide 114 Initial System Configuration Additional Configuration Tasks ...
Page 164: ...ASR 5500 Installation Guide 148 Replaceable Components Returning Failed Components ...
Page 186: ...ASR 5500 Installation Guide 170 Console Port to Cisco Server Cabling Configuration ...
Page 192: ...ASR 5500 Installation Guide 176 RMA Shipping Procedures Rear Cards ...