(4) FSCs [4x150w] = 600 watts
(2) SSCs [2x10w] = 20 watts
Fan Units [front and rear] = 2000 watts
Total = approximately 10 kW
Central Office Alarm Interface
The Central Office (CO) alarm interface on the SSC is a DB15 connector that supports three dry-contact (no
voltage supplied) relay switches. Each of the Form C relays is rated to support a maximum switching current
of 1A@30VDC.
The alarm relay contacts should never be connected to high current draw devices, such as sirens or flashing
incandescent lamps.
Caution
The three relays support both normally-open (NO) and normally-closed (NC) devices. For additional
information, refer to the
SSC Alarm Cabling
chapter for details.
Chassis Grounding
The ASR 5500 is suitable for installation as part of the Common Bonding Network (CBN) within a network
telecommunications facility. It is not intended for installation in an Isolated Bonding Network (IBN).
ASR 5500 Installation Guide
23
Technical Specifications
Central Office Alarm Interface
Summary of Contents for ASR 5500
Page 12: ...ASR 5500 Installation Guide xii Contents ...
Page 16: ...ASR 5500 Installation Guide xvi About this Guide Contacting Customer Support ...
Page 40: ...ASR 5500 Installation Guide 24 Technical Specifications Chassis Grounding ...
Page 74: ...ASR 5500 Installation Guide 58 Card Installation Save Shipping Cartons ...
Page 88: ...ASR 5500 Installation Guide 72 MIO Port Cabling Cleaning Fiber Optic Connectors ...
Page 112: ...ASR 5500 Installation Guide 96 System Power up show leds Command ...
Page 130: ...ASR 5500 Installation Guide 114 Initial System Configuration Additional Configuration Tasks ...
Page 164: ...ASR 5500 Installation Guide 148 Replaceable Components Returning Failed Components ...
Page 186: ...ASR 5500 Installation Guide 170 Console Port to Cisco Server Cabling Configuration ...
Page 192: ...ASR 5500 Installation Guide 176 RMA Shipping Procedures Rear Cards ...