Value
Description
Maximum Input Power
14,667 watts (14.7 kW) 88% efficiency
Modular configuration, DC, chassis fully
loaded
14,348 watts (14.4 kW) 92% efficiency
Modular configuration, AC, chassis fully
loaded
Maximum Output Power
13,200 W (13.2 kW)
Chassis fully loaded (DC and AC)
Power Redundancy
2N: Up to 8 “A” battery plant feeds and up to 8 “B” battery
plant feeds
DC
2N: Up to 6 “A” AC single-phase power sources and up to 6
“B” single-phase AC power sources required.
AC
DC Input
–48 VDC North America–60 VDC International Range: 40 to
–72 VDC
Nominal input voltage
40 A max at –48 VDC30 A max at –60 VDC50 A at –40 VDC
(maximum)
Input current
Single-phase
AC Input
200 to 240 VAC (range 180 to 264 VAC)
Nominal input voltage
50/60 Hz (range 47 to 63 Hz)
Nominal line frequency
20 A (North America) dedicated branch circuit16 A
(International) dedicated branch circuit
Recommended AC service
Line Card Chassis Environmental Specifications
The table lists the environmental specifications for the line card chassis.
Table 10: Line Card Chassis Environmental Specifications
Value
Description
Operating, nominal: 41° to 104°F (5° to 40°C)
Operating, short-term: 23° to 122°F (–5° to 50°C)
Nonoperating: –40° to 158°F (–40° to 70°C)
Temperature
Cisco CRS Routers 16-Slot Line Card Chassis Installation Guide
237
Technical Specifications
Line Card Chassis Environmental Specifications