A-3
Firepower 7000 Series Hardware Installation Guide
Appendix A Power Requirements for Firepower 7000 Series Devices
Firepower 71xx Family Appliances
Bonding Location
A ground bonding location is provided on the rear of the chassis. An M4 stud is provided. An
outside-toothed lock washer is provided for attaching a ring terminal. A standard ground symbol is
available by each stud.
The following illustration indicates the bonding location on the chassis.
Recommended Terminals
You must use a UL-Approved terminal for the ground connection. A ring terminal with a clearance hole
for #6 (M3.5) stud may be used. For 16 AWG wire, AMP/Tyco 36151 is recommended. This is a
UL-approved ring terminal with a hole for a #6 stud.
Ground Wire Requirements
The ground wire must be sized sufficiently to handle the current of the circuit in case of a single fault.
The size of the ground wire should be equal to the current of the breaker used to protect the circuit. See
Bare conductors must be coated with antioxidant before crimp connections are made. Only copper cables
can be used for grounding purposes.
Firepower 71xx Family Appliances
This section describes the power requirements for:
•
Firepower 7110 and 7120 (GERY-1U-8-AC)
•
Firepower 7115 and 7125 (GERY-1U-4C8S-AC)
These appliances are suitable for installation by qualified personnel in network telecommunication
facilities and locations where the National Electric Code applies. Note that each is available only as an
AC appliance.
Cisco recommends that you save the packing materials in case a return is necessary.
For more information, see the following sections:
•
for circuit installation, voltage, current, and frequency range, and power
cord information.
•
See
Grounding/Earthing Requirements, page A-5
for bonding locations, recommended terminals,
and ground wire requirements.