When the mux/demux panel is installed in the ETSI 600x300 cabinet, only the lateral ground position
must be used.
Note
Install and Route Fiber-Optic and USB Cables
All connectors are on the front of the mux/demux patch panel and are equipped with LC bulkhead adapters
and with a USB Type A receptacle connector for inventory purpose. For port label description, see
. The LC-LC patch cords are used to connect the mux/demux patch panel to the NCS 1010 chassis.
Invisible laser radiation may be emitted from disconnected fibers or connectors. Do not stare into beams
or view directly with optical instruments.
Statement 1051
Warning
Always clean all fiber connectors thoroughly before making the connection with the mating adapter. Very
small particles can permanently damage the end of the mating fiber inside the patch panel, which makes
regular cleaning imperative. For cleaning instructions see
Clean Fiber-Optic Cable Connectors, on page 12
Note
The mux/demux patch panel has LC bulkhead adapters for optical connections. Always use fiber-optic cables
equipped with the corresponding LC connector type. Using any other type of connector results in damage to
the connector or adapter, or both.
Caution
This task describes the steps to install and route the fiber-optic and USB cables from the mux/demux patch
panel.
Procedure
Step 1
To connect the fibers as appropriate, perform the following:
a) Remove the LC adapter cap from the LC-LC adapter of the mux/demux patch panel.
b) Place the LC/UPC cable connector in front of the corresponding bulkhead adapter on the front panel of
the mux/demux patch panel.
c) Align the keyed ridge of the cable connector with the slot in the receiving adapter.
d) Gently push the cable connector into the adapter until you hear a click, which indicates that the latching
system is engaged.
e) Route the cables through the left or right fiber holder clip.
f)
(Optional) Secure the fibers further by placing them into one or more adhesive clips. The adhesive clips
can be placed on the fiber management plate as per the actual installation conditions.
g) Place the extra fiber length of the two LC-LC patch cords used to connect the patch panel with its plugged
mux/demux patch panel.
Step 2
To secure the fibers, bundle the fibers using one of the four velcro strips that is provided.
Install Cisco NCS 1000 32-Channel Mux/Demux Patch Panel
10
Install Cisco NCS 1000 32-Channel Mux/Demux Patch Panel
Install and Route Fiber-Optic and USB Cables