Figure 40: Rating Label for AC Power
The voltage rating value for AC power ranges either between 200 V to 240 V or between 100 V to 127 V
depending on the standards in various countries.
A dual pole breaker is needed for the installation. The rating of the dual pole breaker for each feed is 16A for
input voltage 200 Vac to 240 Vac, and 20A for input voltage 100 Vac to 127 Vac.
Note
Step 1
Verify that the AC cable is installed in the correct AC source panel. Ensure that either the fuse is removed or the circuit
breaker is in the off position and locked out.
Step 2
Attach the AC power cable to the cable connector in the AC power module.
Ensure that there is a minimum gap of 50 mm for routing the cables. Use a 90-degree exit cable to maintain a
footprint of 600 mm for ETSI racks.
Note
Step 3
Close the cable retention clips to secure the power cables and to prevent their accidental removal.
Hardware Installation Guide for Cisco NCS 1004
44
Install Cisco NCS 1004 Modules
Connect AC Power to NCS 1004