To install chassis (front): 48 in. (122 cm)
To service FRUs (front): 31.7 in. (80.5 cm)
To service FRUs (rear): 14.0 in. (35.6 cm)
Aisle spacing
Weights
250 lb (113.5 kg)
Chassis as shipped
319 lb (145 kg)
Chassis in shipping crate with pallet
412 lb (187 kg)
Chassis, fully loaded with power, fan trays, cards,
and cosmetics
Floor Loading
Chassis: 2.5 sq ft (0.23 sq m)
Chassis in rack footprint(floor contact area)
263 lb/sq ft
Maximum floor loading
Two fan trays
Chassis Cooling
45,300 liters per minute
Chassis airflow
6796 liters per minute
DC power system airflow
5097 liters per minute
AC power system airflow
Power Specifications
Table 21: Cisco NCS 4016 Chassis Power Specifications
Power Specifications
Either two AC or two DC power trays (cannot mix
AC and DC power trays)
Power Trays
Up to four DC PMs per tray
DC power tray
Up to four AC PMs per tray
AC power tray
Power Redundancy
Up to 8 power modules can be installed, and only
7are needed to be active at any time. This allows
support for 7+1 power redundancy and A and B
battery plant dual feeds redundancy.
DC
Hardware Installation Guide for Cisco NCS 4000 Series
144
System Specifications
Power Specifications