Either two AC or two DC power trays (cannot mix AC
and DC power trays)
Power Trays
Up to 8 power modules can be installed, and only 4
are needed to be active at any time. This allows
support for 4+4 power redundancy and A and B
battery plant dual feeds redundancy.
DC
Up to 8 power modules can be installed, and only 3
are needed to be active at any time. This allows
support for 3+5 power redundancy by using two
independent AC power sources (4 feeds each).
AC
DC Input
–
48 VDC or
–
60 VDC(tolerance range:
–
40.5VDC
to
–
72 VDC)
Nominal input voltage
37 A max at
–
48 VDC29.6 A max at
–
60 VDC43.9
A max at
–
40.5 VDC
Input current
12 A max per feed
AC Input
200 to 240 VAC (range 180 to 264 VAC)
Nominal input voltage
50/60 Hz (range 47 to 63 Hz)
Nominal line frequency
30-A (North America) dedicated branch circuit30-A
(International) dedicated branch circuit
Recommended AC service
167 in. (4.25 m)
AC Power Cord Length
Environmental Specifications
This table describes the environmental specifications of the Cisco NCS 4009 chassis.
Table 42: Cisco NCS 4009 Chassis Environmental Specifications
Operating, nominal: 41 to 104°F (5° to 40°C)
Operating, short-term: 23 to 131°F (
–
5° to 55°C)
Nonoperating:
–
40 to 158°F (
–
40° to 70°C)
Temperature
Operating, nominal: 5 to 85%, noncondensing
Operating, short-term: 5 to 90%, noncondensing
Nonoperating: 5 to 93%, noncondensing
Humidity
Hardware Installation Guide for Cisco NCS 4000 Series
275
System Specifications
Environmental Specifications