Figure 45: Attaching to Side NEBS Bonding and Grounding Point in the NCS 4009
Step 3
Use the torque wrench to tighten the bolts to a torque of 35 in-lb (3.95 N-m).
Step 4
Connect the other end of the ground cable to a grounding point at your site, according to site requirements.
Installing an AC or DC Power Tray
The power tray is preinstalled on the chassis. The following procedure describes how to install an AC or DC
power tray in the chassis.
Tools and Equipment
• 6-inch, number-2 Phillips screwdriver
Hardware Installation Guide for the Cisco NCS 4000 Series
62
Installing Power Components
Installing an AC or DC Power Tray