To connect the NCS-950W-DCFW power supply module with the power source, use a copper wire that is
14AWG or lesser in size.
Note
Step 6
Ensure that the locking mechanism has engaged to secure the cable.
Step 7
Turn on the circuit breaker at the power source.
Power Supply Unit Input and Output Ranges
This table summarises input and output power ranges for PSU low line and nominal applications:
Table 8: Input and output power ranges for PSUs
Output
Output Power
Input Current (Max)
Input Voltage
PID
12V/84A
1000W
12A
100 to 127V ac
PSU2KW-ACPI
For low line
applications
12V/167A
2000W
12A
200 to 240V ac
PSU2KW-ACPI
For nominal voltage
application
12V/167A
2000W
40A
-40V to - 72V DC
PSU2KW-DCPI
12V/90A
1100W
12A
100V to 240V ac
NCS-1100W-ACFW
For port side intake
For nominal voltage
application
12V/79A
950W
26A
-40V to - 72V DC
NCS-950W-DCFW
For port side intake
For nominal voltage
application
Install the Chassis
43
Install the Chassis
Power Supply Unit Input and Output Ranges