people. To lighten the chassis for lifting, you can remove the power supplies so that the chassis weighs no
more than 93 pounds (42 kg) and can be lifted by two people.

After lifting the chassis into position, you fasten it to the rack, and replace any power supplies that you might
have removed earlier.

To install a Cisco Nexus 7004 chassis in a two- or four-post rack or cabinet, follow these steps:

SUMMARY STEPS

1.

Prepare the chassis for moving by doing one of the following:

2.

Lift the chassis to its position on a rack in one of the following ways:

3.

Use five M6 x 19 mm screws (or 12-24 x 3/4 inch screws) to fasten each side of the chassis to the rack.
Tighten each of the 10 screws to 40 in. lbs (4.5 N.m) (see

Figure 2: Mounting the Cisco Nexus 7004

Chassis on a Rack, on page 7

).

4.

If you removed any power supplies, replace them as explained in one of the following sections:

DETAILED STEPS

Step 1

Prepare the chassis for moving by doing one of the following:

To prevent personal injury or damage to the chassis, never attempt to lift or tilt the chassis using the handles
on modules (such as power supplies, fans, or cards); these types of handles are not designed to support the
weight of the unit. Statement 1032

Danger

To move the chassis, either use the chassis handles (one found on each side) or push on the sides or edges of
the chassis without touching any of the modules or module handles.

Caution

• To move the chassis with a mechanical lift, position the lift at the elevation of the chassis on its shipping pallet (or

no more than 0.25 inches [0.64 cm] below the level of the pallet) and use two persons to push the chassis fully onto
the lift.

• To move the chassis manually, remove the power supplies as explained in one of the following sections and then

use two persons to lift the chassis:

• To remove an AC power supply, see the

“Removing a 3-kW AC Power Supply Unit During Operations” section

on page 10-3

.

• To remove a DC power supply, see the

“Removing a 3-kW DC Power Supply Unit During Operations” section

on page 10-9

.

• To remove an HVAC/HVDC power supply, see the

“Removing a 3.5-kW HVAC/HVDC Power Supply Unit

During Operations” section on page 10-16

.

We do not recommend that you remove any of the supervisor modules, I/O modules, or the fan tray to make
the chassis easier to lift because that removal can put those modules at risk of being damaged. If you do remove
any of those modules, be sure to have antistatic pads or antistatic bags to hold these modules until you are ready
to reinstall them in the chassis.

Note

Step 2

Lift the chassis to its position on a rack in one of the following ways:

• If you use a mechanical lift, position the chassis next to the front of another Cisco Nexus 7004 chassis already

installed in the rack, elevate the new chassis to the level of the installed chassis (or no more than 0.25 inches [0.64

Installing a Cisco Nexus 7004 Chassis

6

Installing a Cisco Nexus 7004 Chassis

Installing the Chassis in a Rack

Summary of Contents for Nexus 7004

Page 1: ...19 inch EIA rack or cabinet before you can install the Cisco Nexus 7004 chassis Make sure that you order the rack or cabinet and have it delivered before installing the chassis Note Required Tools Before you install the Cisco Nexus 7004 chassis into a rack make sure that you have the Cisco Nexus 7004 Accessory Kit see the Cisco Nexus 7004 Switch Accessory Kit section on page C 1 for the contents l...

Page 2: ... mechanism must be in place or the rack must be bolted to the floor before you slide the unit out for servicing Failure to stabilize the rack can cause the rack to tip over Statement 1048 Warning If the rack has bonded construction connect it to the earth ground to enable you to easily ground the system components that you install and to ground your ESD wrist strap This step minimizes the chance o...

Page 3: ...all of the ordered items The shipment should include boxes for the following System chassis which includes the following installed components 2 supervisor modules 1 or 2 I O modules 1 fan tray 2 to 4 power supply units Blank filler plates for any missing supervisor modules I O modules or power supply modules Cisco Nexus 7004 system accessory kit To see a list of what is in the accessory kit see th...

Page 4: ...post 19 inch EIA rack or cabinet that includes such a rack For more information on the rack or cabinet see the Installing a Rack or Cabinet on page 2 Stability hazard The rack stabilizing mechanism must be in place or the rack must be bolted to the floor before you slide the unit out for servicing Failure to stabilize the rack can cause the rack to tip over Statement 1048 Warning To prevent bodily...

Page 5: ...Installing Center Mount Brackets on the Chassis on page 5 Figure 1 Installing Center Mount Brackets on the Chassis Six M4 x 6 mm screws for each bracket 2 Center mount bracket left and right versions 1 Step 2 Use a Phillips head screw driver to secure the bracket to the chassis with the six M4 x 6 mm screws Tighten each screw to 11 5 to 15 in lbs 1 3 to 1 7 N m Step 3 Repeat steps 1 and 2 to insta...

Page 6: ...es or module handles Caution To move the chassis with a mechanical lift position the lift at the elevation of the chassis on its shipping pallet or no more than 0 25 inches 0 64 cm below the level of the pallet and use two persons to push the chassis fully onto the lift To move the chassis manually remove the power supplies as explained in one of the following sections and then use two persons to ...

Page 7: ...using the handle on each side of the chassis Do not use the handles on any of the modules installed on the chassis to lift or move the chassis these handles are for only removing or installing the modules Caution Step 3 Use five M6 x 19 mm screws or 12 24 x 3 4 inch screws to fasten each side of the chassis to the rack Tighten each of the 10 screws to 40 in lbs 4 5 N m see Figure 2 Mounting the Ci...

Page 8: ...e modules This grounding system is active even when the AC power cables are not connected to the system Note You connect the AC power supplies to the earth ground automatically when you connect an AC power supply to an AC power source You connect the DC power supplies to the earth ground before connecting the power supplies to the DC power source see the Connecting a DC Power Supply Directly to DC...

Page 9: ...th 0 75 in 19 mm of insulation stripped from the end 2 NRTL listed 45 degree grounding lug 1 Step 3 Use the crimping tool to crimp the lug to the grounding wire Verify that the ground wire is securely attached to the ground lug by attempting to pull the wire out of the crimped lug Step 4 Remove the adhesive label from the system grounding pad on the chassis secure the grounding wire lug to the gro...

Page 10: ... strap by plugging it into the ESD port shown by Callout 2 in Figure 4 Grounding Pad and ESD Port Locations on the Cisco Nexus 7004 Chassis on page 10 Installing the Cable Management Frames After you have fastened the chassis to the rack you can fasten the cable management frames to the front of the chassis To fasten the cable management frames to the chassis follow these steps SUMMARY STEPS 1 Ali...

Page 11: ...should be at the same level as the top of the chassis see Figure 5 Installing the Cable Management Frames on a Cisco Nexus 7004 Chassis on page 11 Figure 5 Installing the Cable Management Frames on a Cisco Nexus 7004 Chassis Three M3 x 10 mm screws used to fasten the frame to the chassis total of six screws for two frames 2 Guide pins on the cable management frame aligned to two holes in the front...

Page 12: ...SB drive into the expansion flash reader the message will end with slot0 online If you see an offline message or do not see a message either the USB drive is not fully inserted or it is improperly formatted Make sure that the USB drive is fully inserted inside the reader If it is fully inserted either format the card see the Cisco Nexus 7000 Series NX OS Fundamentals Configuration Guide or replace...

Reviews: