Step 4

If you removed any power supplies, replace them as explained in one of the following sections:

• To install an AC power supply unit, see the “Installing a 3-kW AC Power Supply Unit During Operations” section.

• To install a DC power supply unit, see the “Installing a 3-kW DC Power Supply Unit During Operations” section.

• To install a HVAC/HVDC power supply unit, see the “Installing a 3.5-kW HVAC/HVDC Power Supply Unit During

Operations” section.

Grounding the Cisco Nexus 7004 Chassis

The Cisco Nexus 7004 switch is fully grounded as soon as you connect the chassis and the power supplies to
the earth ground in the following ways:

• You connect the chassis to either a grounded and fully bonded rack or to the data center ground. This

ground connection is active even when the power supplies are not installed.

The system ground, also referred to as the network equipment building system (NEBS) ground, provides
additional grounding for EMI shielding requirements and for the low-voltage supplies (DC-DC converters)
on the modules. This grounding system is active even when the AC power cables are not connected to the
system.

Note

• You connect the AC power supplies to the earth ground automatically when you connect an AC power

supply to an AC power source.

• You connect the DC power supplies to the earth ground before connecting the power supplies to the DC

power source (see the

“Connecting a DC Power Supply Directly to DC Power Sources” section on page

6-11

).

• You automatically ground an HVAC/HVDC power supply when you connect the HVAC/HVDC power

supply to a power source.

This section includes the following topics:

Prerequisites for Grounding the Chassis

Before you can ground the chassis, you must have a connection to the earth ground for the data center building.
If you installed the Cisco Nexus 7004 chassis into a bonded rack (see the rack manufacturer’s instructions for
more information) that now has a connection to the data center earth ground, you can ground the chassis by
connecting its grounding port to the rack. Otherwise, you must connect the chassis grounding port directly to
the data center ground.

Installing a Cisco Nexus 7004 Chassis

8

Installing a Cisco Nexus 7004 Chassis

Grounding the Cisco Nexus 7004 Chassis

Summary of Contents for Nexus 7004

Page 1: ...19 inch EIA rack or cabinet before you can install the Cisco Nexus 7004 chassis Make sure that you order the rack or cabinet and have it delivered before installing the chassis Note Required Tools Before you install the Cisco Nexus 7004 chassis into a rack make sure that you have the Cisco Nexus 7004 Accessory Kit see the Cisco Nexus 7004 Switch Accessory Kit section on page C 1 for the contents l...

Page 2: ... mechanism must be in place or the rack must be bolted to the floor before you slide the unit out for servicing Failure to stabilize the rack can cause the rack to tip over Statement 1048 Warning If the rack has bonded construction connect it to the earth ground to enable you to easily ground the system components that you install and to ground your ESD wrist strap This step minimizes the chance o...

Page 3: ...all of the ordered items The shipment should include boxes for the following System chassis which includes the following installed components 2 supervisor modules 1 or 2 I O modules 1 fan tray 2 to 4 power supply units Blank filler plates for any missing supervisor modules I O modules or power supply modules Cisco Nexus 7004 system accessory kit To see a list of what is in the accessory kit see th...

Page 4: ...post 19 inch EIA rack or cabinet that includes such a rack For more information on the rack or cabinet see the Installing a Rack or Cabinet on page 2 Stability hazard The rack stabilizing mechanism must be in place or the rack must be bolted to the floor before you slide the unit out for servicing Failure to stabilize the rack can cause the rack to tip over Statement 1048 Warning To prevent bodily...

Page 5: ...Installing Center Mount Brackets on the Chassis on page 5 Figure 1 Installing Center Mount Brackets on the Chassis Six M4 x 6 mm screws for each bracket 2 Center mount bracket left and right versions 1 Step 2 Use a Phillips head screw driver to secure the bracket to the chassis with the six M4 x 6 mm screws Tighten each screw to 11 5 to 15 in lbs 1 3 to 1 7 N m Step 3 Repeat steps 1 and 2 to insta...

Page 6: ...es or module handles Caution To move the chassis with a mechanical lift position the lift at the elevation of the chassis on its shipping pallet or no more than 0 25 inches 0 64 cm below the level of the pallet and use two persons to push the chassis fully onto the lift To move the chassis manually remove the power supplies as explained in one of the following sections and then use two persons to ...

Page 7: ...using the handle on each side of the chassis Do not use the handles on any of the modules installed on the chassis to lift or move the chassis these handles are for only removing or installing the modules Caution Step 3 Use five M6 x 19 mm screws or 12 24 x 3 4 inch screws to fasten each side of the chassis to the rack Tighten each of the 10 screws to 40 in lbs 4 5 N m see Figure 2 Mounting the Ci...

Page 8: ...e modules This grounding system is active even when the AC power cables are not connected to the system Note You connect the AC power supplies to the earth ground automatically when you connect an AC power supply to an AC power source You connect the DC power supplies to the earth ground before connecting the power supplies to the DC power source see the Connecting a DC Power Supply Directly to DC...

Page 9: ...th 0 75 in 19 mm of insulation stripped from the end 2 NRTL listed 45 degree grounding lug 1 Step 3 Use the crimping tool to crimp the lug to the grounding wire Verify that the ground wire is securely attached to the ground lug by attempting to pull the wire out of the crimped lug Step 4 Remove the adhesive label from the system grounding pad on the chassis secure the grounding wire lug to the gro...

Page 10: ... strap by plugging it into the ESD port shown by Callout 2 in Figure 4 Grounding Pad and ESD Port Locations on the Cisco Nexus 7004 Chassis on page 10 Installing the Cable Management Frames After you have fastened the chassis to the rack you can fasten the cable management frames to the front of the chassis To fasten the cable management frames to the chassis follow these steps SUMMARY STEPS 1 Ali...

Page 11: ...should be at the same level as the top of the chassis see Figure 5 Installing the Cable Management Frames on a Cisco Nexus 7004 Chassis on page 11 Figure 5 Installing the Cable Management Frames on a Cisco Nexus 7004 Chassis Three M3 x 10 mm screws used to fasten the frame to the chassis total of six screws for two frames 2 Guide pins on the cable management frame aligned to two holes in the front...

Page 12: ...SB drive into the expansion flash reader the message will end with slot0 online If you see an offline message or do not see a message either the USB drive is not fully inserted or it is improperly formatted Make sure that the USB drive is fully inserted inside the reader If it is fully inserted either format the card see the Cisco Nexus 7000 Series NX OS Fundamentals Configuration Guide or replace...

Reviews: