Cisco Nexus 7000 Series Hardware Installation and Reference Guide
OL-23069-06
Chapter 9 Replacement Procedures
Replacing the Front Door and Air Intake Assemblies on the Cisco Nexus 7018 Chassis
Figure 9-42
Attaching the Right Door Stopper
Step 4
Position the bottom hinge bracket at the bottom of both sides of the cable management frame. Make sure
that the side of the bracket that is closest to the chassis has two alignment pins that align with the
alignment holes in the chassis as shown in
. Push the bracket toward the chassis so that its
alignment pins enter the alignment holes and the bracket rests against the chassis.
1
Right door stopper identified with an R on
the bottom of the base.
3
Screw holes on the right side of the cable
management frame.
2
Two M3x14 screws that fasten the stopper
to the right side of the cable management
assembly.