S e n d d o c u m e n t c o m m e n t s t o n e x u s 7 k - d o c f e e d b a c k @ c i s c o . c o m
A-19
Cisco Nexus 7000 Series Hardware Installation and Reference Guide
OL-23069-06
Appendix A Technical Specifications
Chassis Airflow
Table A-15
Airflow for a Fully Configured Cisco Nexus 7009 Switch
Temperature
System Airflow
(cfm)
Fabric Airflow
(cfm)
Total Airflow
(cfm)
<55ºF (13ºC)
686
76
762
55 to 62ºF (13 to 17ºC)
686
92
778
64 to 71ºF (18 to 22ºC)
686
107
793
73 to 80ºF (23 to 27ºC)
686
123
809
82 to 89ºF (28 to 32ºC)
686
143
829
91 to 98ºF (33 to 37ºC)
768
153
921
100 to 107ºF (38 to 42ºC) 842
173
1015
109 to 116ºF (43 to 47ºC) 1044
189
1233
118 to 125ºF (48 to 52ºC) 1203
203
1406
127 to 136ºF (53 to 58ºC) 1326
221
1547
>136ºF (>58ºC)
1203
250
1576
Table A-16
Airflow for a Fully Configured Cisco Nexus 7010 Switch
Temperature
System Airflow
(cfm)
Fabric Airflow
(cfm)
Total Airflow
(cfm)
<55ºF (13ºC)
406
37
443
55 to 62ºF (13 to 17ºC)
493
44
537
64 to 71ºF (18 to 22ºC)
534
50
584
73 to 80ºF (23 to 27ºC)
576
56
632
82 to 89ºF (28 to 32ºC)
659
63
722
91 to 98ºF (33 to 37ºC)
744
70
814
100 to 107ºF (38 to 42ºC) 853
75
928
109 to 116ºF (43 to 47ºC) 1044
100
1144
118 to 125ºF (48 to 52ºC) 1242
154
1396
127 to 136ºF (53 to 58ºC) 1447
162
1609
>136ºF (>58ºC)
1447
162
1609
Table A-17
Airflow for a Fully Configured Cisco Nexus 7018 Switch
Temperature
System Airflow
(cfm)
Fabric Airflow
(cfm)
Total Airflow
(cfm)
<55ºF (13ºC)
1459
71
1530
55 to 62ºF (13 to 17ºC)
1459
83
1542