Figure 5: Inserting the Grounding Wire in the Grounding Lug
Grounding cable with 0.75 in. (19 mm) of insulation stripped from the end
2
NRTL listed 45-degree grounding lug
1
Step 3
Use the crimping tool to crimp the lug to the grounding wire. Verify that the ground wire is securely attached to the
ground lug by attempting to pull the wire out of the crimped lug.
Step 4
Remove the adhesive label from one of the two system grounding pads, and secure the grounding wire lug to the grounding
pad with two M4 screws.
Figure 6: Grounding Pad on the Cisco Nexus 7018 Chassis, on page 15
shows the location of
the grounding pad on the front side of the chassis. Ensure that the grounding lug and the grounding wire do not interfere
with other switch hardware or rack equipment.
Installing a Cisco Nexus 7018 Chassis
14
Installing a Cisco Nexus 7018 Chassis
Connecting the System Ground