background image

Replacing Modules

Replacing a Fan Module, on page 1

Replacing a Power Supply Module, on page 2

Replacing a Fan Module

You can replace a fan module while the switch is operating so long as you perform the replacement within
one minute. If you cannot perform the replacement within one minute, leave the original fan module in the
chassis to maintain the designed airflow until you have the replacement fan module on hand and can perform
the replacement.

If you are replacing a module during operations, be sure that the replacement fan module has the correct
direction of airflow, which means that it has the same airflow direction as the other modules in the chassis.
Also, be sure that the airflow direction takes in air from a cold aisle and exhausts to a hot aisle. Otherwise,
the switch can overheat and shutdown.

If you are changing the airflow direction of all the modules in the chassis, you must shutdown the switch
before replacing all the fan and power supply modules with modules using the other airflow direction. During
operations, all of the modules must have the same direction of airflow.

Caution

Removing a Fan Module

Statement 263—

Fan Warning

The fans might still be turning when you remove the fan assembly from the chassis. Keep fingers, screwdrivers,
and other objects away from the openings in the fan assembly's housing.

Warning

Step 1

On the fan module that you are removing, press the two sides of the fan module handle next to where it connects to the
fan module and pull on the handles enough to unseat it from its connectors.

Step 2

Holding the handle, pull the module out of the chassis.

Replacing Modules

1

Summary of Contents for Nexus 93108TC-EX

Page 1: ... in air from a cold aisle and exhausts to a hot aisle Otherwise the switch can overheat and shutdown If you are changing the airflow direction of all the modules in the chassis you must shutdown the switch before replacing all the fan and power supply modules with modules using the other airflow direction During operations all of the modules must have the same direction of airflow Caution Removing...

Page 2: ...requires two power supplies for redundancy With one power supply providing the necessary power for operations you can replace the other power supply during operations so long as the new power supply has the same airflow direction as the other modules in the chassis You can replace a power supply with another supported power supply that has the same power source type and the same wattage rating as ...

Page 3: ...ly Removing an HVAC HVDC Power Supply You can remove one power supply while the other one provides power to the switch To disconnect the power supply from its power cables you must shut off the power from the power source and then either disconnect a connector for the power cables or release each of three cables from the power supply requires a standard screw driver Step 1 Turn off the circuit bre...

Page 4: ...the power supply handle while pressing the release latch towards the power supply handle Step 4 Pull the power supply out of the bay What to do next You are ready to install a DC power supply in the open slot Installing an AC Power Supply You can replace one power supply while the other one provides power to the switch Before you begin The power supply that you are installing must be capable of us...

Page 5: ... until it clicks in place Step 3 Attach the power cable to the electrical outlet on the front of the power supply Step 4 Make sure that the other end of the power cable is attached to the appropriate power source for the power supply Depending on the outlet receptacle on your power distribution unit you might need the optional jumper cable to connect the switch to your outlet receptacle Note Step ...

Page 6: ...lectrical connector block insert the block into the power receptacle on the power supply If the electrical cables have not been connected to the electrical connector block wire them as described in Wiring a 48 V DC Electrical Connector Block on page 7 Step 4 Make sure that the other end of the power cable is connected to the appropriate power source for the power supply Step 5 If using a DC power ...

Page 7: ...block insert the block into the power receptacle on the power supply If the electrical cables have not been connected to the electrical connector block wire them as described in Wiring a 48 V DC Electrical Connector Block on page 7 Step 3 Turn on the circuit breaker for the DC power source connected to the power supply Step 4 Verify that the power supply is operational by making sure that the powe...

Page 8: ...turn DC cable 3 Step 5 Use a small screwdriver to depress the spring loaded wire retainer lever on the lower spring cage wire connector Insert your green ground wire into the aperture and then release the lever Step 6 Use a small screwdriver to depress the spring loaded wire retainer lever on the middle spring cage wire connector Insert your black DC negative wire into the aperture and then releas...

Reviews: