1-5
Cisco ONS 15454 DWDM Procedure Guide, R8.0
78-17704-02
Chapter 1 Install the Shelf and Common Control Cards
Required Tools and Equipment (ETSI)
Required Tools and Equipment (ETSI)
You need the following tools and equipment to install and test the ONS 15454 ETSI shelf assembly.
Cisco-Supplied Equipment (ETSI)
These materials are required for installation and are supplied with the ONS 15454 ETSI. The shipped
quantity of each item is in parentheses.
•
Double-hole grounding lug for ground connection with a wire receptacle to accommodate the
recommended 13.3 mm² (#6 AWG) multistrand copper wire (1)
•
M4 x 8 mm pan-head Phillips screws (2)
•
M6 x 20 mm socket set screws (2)
•
M6 x 20 mm pan-head Phillips screws (8)
•
Tie wraps 0.125-inch (3.2 mm) W x 6.0-inch (152 mm) L (24)
•
ESD wrist strap (disposable) (1)
•
Pinned hex (Allen) key for front door (1)
•
Hex key 3-mm long arm (1)
•
Bottom brackets for the fan-tray air filter
•
Cable assembly, Ethernet, RJ-45 (1)
•
Power cable (from fuse and alarm panel to MIC-A/P and MIC-C/T/P) (2)
Caution
Only use the power cables that are designed to be used with ONS 15454 ETSI. They are sold separately.
User-Supplied Equipment (ETSI)
The following materials and tools are required for installation but are not supplied with the
ONS 15454 ETSI:
•
Equipment rack (ETSI rack, 2200 mm [86.6 inch] H x 600 mm [23.6 inch] W
x 300 mm [11.8 inch] D)
•
Fuse and alarm panel
•
Copper ground cable 13.3-mm² (#6 AWG) stranded, specified for up to 90 degrees Celsius
(194 degrees Fahrenheit)
•
Alarm cable pairs for all alarm connections, 0.51 mm² or 0.64 mm² (#22 or #24 AWG), solid-tinned
•
Single-mode SC fiber jumpers with UPC polish (55 dB or better) for optical cards
•
Coaxial cable terminated with 1.0/2.3 miniature coax connectors for FMEC cards
•
DB-37 cable
•
Shielded BITS clock coaxial cable terminated with 1.0/2.3 miniature coax connectors
•
Labels
•
Wire wrapper