Procedure
Step 1
Place the right front air deflector flush against the right side of the chassis as shown in Diagram 1 of
Step 2
Align the screw holes on the right front air deflector with the screw holes on right side of the chassis.
Step 3
Insert the screws and tighten them to a torque value of 11.5 in-lb (1.3 N-m). See Diagram 2 of
Step 4
Place the left back air deflector flush against the chassis as shown in Diagram 1 of
Air Deflectors (Front-to-Back) on the ONS 15454 M2 Shelf for ETSI Rack Configuration, on page 207
If the 100G-LC-C, 10x10G-LC, or CFP-LC cards are to be installed in the ONS 15454 M2 shelf,
do not mount the left back deflector (exhaust air deflector). Use the standard brackets directly to
mount the ONS 15454 M2 shelf.
Note
Step 5
Align the screw holes on the left back air deflector with the screw holes on the chassis.
Step 6
Insert the screws and tighten them to a torque value of 11.5 in-lb (1.3 N-m). See Diagram 2 of
Step 7
Place the air deflector covers on the front and rear ends of the chassis as shown in Diagram 3 of
Step 8
Align the screw holes on the air deflector covers with the screw holes on the chassis.
Step 9
Insert the screws and tighten them to a torque value of 11.5 in-lb (1.3 N-m). See Diagram 4 of
Step 10
Place the mounting bracket flush in the front position (see Diagram 1 of
Figure 128: Mounting the Brackets
)
or in the middle position (see Diagram 3 of
Figure 128: Mounting the Brackets with Air Deflectors
(Front-to-Back) on the ONS 15454 M2 Shelf for ETSI Rack Configuration, on page 207
) against the right side
of the chassis.
Step 11
Align the screw holes on the 23-inch mounting bracket with the screw holes on the right side of the chassis.
Step 12
Insert the screws and tighten them to a torque value of 11.5 in-lb (1.3 N-m).
Step 13
Place the mounting bracket flush in the front position (see Diagram 1 of
Figure 128: Mounting the Brackets
)
or in the middle position (see Diagram 3 of
Figure 128: Mounting the Brackets with Air Deflectors
(Front-to-Back) on the ONS 15454 M2 Shelf for ETSI Rack Configuration, on page 207
) against the left side
of the chassis.
Step 14
Align the screw holes on the 23-inch mounting bracket with the screw holes on the left side of the chassis.
Step 15
Insert the screws and tighten them to a torque value of 11.5 in-lb (1.3 N-m).
Cisco ONS 15454 Hardware Installation Guide
206
Installing the ONS 15454 M2 Shelf
DLP-G587 Mounting the Bracket with Air Deflectors (Front-to-Back) on the ONS 15454 M2 Shelf for ETSI Rack Configuration
Summary of Contents for ONS 15454
Page 2: ... 2019 Cisco Systems Inc All rights reserved ...
Page 16: ...Cisco ONS 15454 Hardware Installation Guide xvi Contents ...
Page 28: ...Cisco ONS 15454 Hardware Installation Guide xxviii Preface Preface ...
Page 36: ...Cisco ONS 15454 Hardware Installation Guide 6 Overview Cisco ONS 15454 M6 Shelf ...
Page 510: ...Cisco ONS 15454 Hardware Installation Guide 480 Hardware Specifications Dimensions ...