The 15454-M2-FTA2 is compatible with R9.2.0 and later releases.
Note
Do not operate an ONS 15454 M2 shelf without an air filter. For information on the air filter, see
Inspect and Replace the Air Filter, on page 435
Caution
Do not force a fan-tray module into place. Doing so can damage either the connectors on the fan-tray or the
connectors on the backpanel of the shelf, or both.
Caution
Error messages appear on the TNC, TNCE, TSC, or TSCE card, the fan-tray LED, and in the Cisco Transport
Controller (CTC) when the fan-tray module is removed from the shelf or when one fan is not working.
Note
During the system startup or fan-tray replacement, the inventory data of the fan-tray assembly and the power
module is displayed in the
Inventory
tab of CTC after a delay of approximately 6 minutes.
Note
To install the fan-tray assembly, it is not necessary to move any of the fiber-routing facilities.
Note
Procedure
Step 1
Insert the fan-tray assembly in Slot B of the ONS 15454 M2 chassis (see the following figure).
Figure 158: Installing the Fan-Tray Assembly
Cisco ONS 15454 Hardware Installation Guide
236
Installing the ONS 15454 M2 Shelf
NTP-G268 Install the Fan-Tray Assembly in the ONS 15454 M2 Shelf