Pinned hex key
# 2 Phillips Dynamometric screwdriver
ETSI only:
Two M6 x 20 socket set screws
Eight M6 x 20 pan-head Phillips mounting screws
ANSI only:
Two #12-24 x 3/4 set screws (48-1003-XX)
Eight #12-24 x 3/4 pan-head Phillips mounting screws (48-1004-XX, 48-1007-XX)
Tools/Equipment
NTP-G305 Unpack and Inspect the ONS 15454, ONS 15454 M2, and ONS 15454
M6 Shelves, on page 20
Prerequisite Procedures
As needed
Required/As Needed
Onsite
Onsite/Remote
None
Security Level
The ONS 15454 ETSI requires 616.5 mm (24.24 inch) minimum of vertical rack space and 25 mm (1 inch)
below the installed shelf to allow air flow to the fan intake. If a second ONS 15454 ETSI is installed above
a shelf, the air ramp between the shelves provides space for air flow. To ensure that the mounting is secure,
use two to four M6 mounting screws for each side of the shelf. A shelf should be mounted at the bottom of
the rack if it is the only unit in the rack.
Note
The ONS 15454 ANSI must have one inch (25.4 mm) of airspace below the installed shelf to allow air flow
to the fan intake. If a second ONS 15454 is installed underneath a shelf, the air ramp on top of the bottom
shelf provides the desired space. However, if the ONS 15454 is installed above third-party equipment, you
must provide a minimum spacing of one inch (25.4 mm) between the third-party shelf and the bottom of the
ONS 15454. The third-party equipment must not vent heat upward into the ONS 15454.
Note
Procedure
Step 1
Verify that the proper fuse and alarm panel has been installed in the top mounting space. If a fuse and alarm
panel is not present, you must install one according to manufacturer’s instructions:
• (ETSI only) Verify that the fuse rating does not exceed 30A.
• The fuse rating for ANSI chassis must not exceed 30A.
Step 2
Ensure that the shelf is set for the desired rack size (either 23 inches [584.2 mm] or 19 inches [482.6 mm]).
Step 3
Using the hex tool that shipped with the assembly, install the two set screws into the holes that will not be
used to mount the shelf. Let the set screws protrude sufficiently to hold the mounting brackets.
Cisco ONS 15454 Hardware Installation Guide
38
Installing the ONS 15454 M12 (ANSI and ETSI) Shelf
DLP-G679 Mount the ONS 15454 Shelf in a Rack (Two People)
Summary of Contents for ONS 15454
Page 2: ... 2019 Cisco Systems Inc All rights reserved ...
Page 16: ...Cisco ONS 15454 Hardware Installation Guide xvi Contents ...
Page 28: ...Cisco ONS 15454 Hardware Installation Guide xxviii Preface Preface ...
Page 36: ...Cisco ONS 15454 Hardware Installation Guide 6 Overview Cisco ONS 15454 M6 Shelf ...
Page 510: ...Cisco ONS 15454 Hardware Installation Guide 480 Hardware Specifications Dimensions ...