Chapter 1 Install the Cisco ONS 15454 Shelf Assembly
Required Tools and Equipment (ETSI)
Caution
Always use the supplied ESD wristband when working with a powered ONS 15454 ETSI. For detailed
instructions on how to wear the ESD wristband, refer to the
Cisco ONS Electrostatic Discharge (ESD)
Step 1
For an ONS 15454 ETSI shelf, complete the following tasks as necessary:
•
Complete the
“DLP-G20 Install Alarm Wires on the MIC-A/P (ETSI Only)” task on page 1-49
if
you want to provision external alarms and/or controls with the AIC-I card.
•
Complete the
“DLP-G21 Install Timing Wires on the MIC-C/T/P (ETSI Only)” task on page 1-52
you are provisioning external timing.
•
Complete the
“DLP-G22 Install LAN Wires on the MIC-C/T/P (ETSI Only)” task on page 1-53
to
create an external LAN connection. You must either install LAN wires on the MIC-C/T/P or connect
a CAT-5 Ethernet cable to the LAN port on the TCC2/TCC2P/TCC3 card to create an external LAN
connection.
Step 2
For an ONS 15454 ANSI shelf, complete the following tasks as necessary:
•
Complete the
“DLP-G23 Install Alarm Wires on the Backplane (ANSI Only)” task on page 1-54
you are using an AIC-I card and are not using an AEP.
•
Complete the
“DLP-G24 Install Timing Wires on the Backplane (ANSI Only)” task on page 1-56
if
you are provisioning external timing.
•
Complete the
“DLP-G25 Install LAN Wires on the Backplane (ANSI Only)” task on page 1-57
create an external LAN connection. You must either install LAN wires on the backplane or connect
a CAT-5 Ethernet cable to the LAN port on the TCC2/TCC2P/TCC3 card to create an external LAN
connection.
•
Complete the
“DLP-G26 Install the TL1 Craft Interface Wires (ANSI Only)” task on page 1-58
to
access Transaction Language One (TL1) using the craft interface. Craft wires or the EIA/TIA-232
port on the TCC2/TCC2P/TCC3 card are required to access TL1.
Stop. You have completed this procedure.
DLP-G20 Install Alarm Wires on the MIC-A/P (ETSI Only)
Purpose
This task installs alarm cables on the MIC-A/P on the ONS 15454 ETSI so
that you can provision external (environmental) alarms and controls with
the AIC-I card.
Tools/Equipment
DB-62 connector
0.51 mm² or 0.64 mm² (#22 or #24 AWG) wires
Prerequisite Procedures
NTP-G6 Install the MIC-A/P and MIC-T/C/P FMECs (ETSI Only),
page 1-31
Required/As Needed
As needed
Onsite/Remote
Onsite
Security Level
None
Summary of Contents for ONS 15454
Page 48: ...Tables xlviii Cisco ONS 15454 DWDM Procedure Guide Release 9 2 78 19286 01 ...
Page 58: ...Procedures lviii Cisco ONS 15454 DWDM Procedure Guide Release 9 2 78 19286 01 ...
Page 78: ...Tasks lxxviii Cisco ONS 15454 DWDM Procedure Guide Release 9 2 78 19286 01 ...
Page 85: ...lxxxv Cisco ONS 15454 DWDM Procedure Guide Release 9 2 78 19286 01 Preface ...
Page 87: ...lxxxvii Cisco ONS 15454 DWDM Procedure Guide Release 9 2 78 19286 01 Preface ...