Dynamic (Preracked with
Side Panels)
Expansion (Static without
Side Panels)
Standard (Static with side
panels)
Cisco R42612 Rack
2700 lb (1224.7 kg) of IT
gear
N/A
N/A
Dynamic load capacity
PDU Specifications
The following specifications are for the PDUs that can be used in the Cisco R42612 rack.
RP208-30M1P-4-8
Table 7: Specifications for RP208-30M1P-4-8 PDU
Description
Feature
RP208-30M1P-4-8
PID
North America
Country
1U
RU size
1.69 x 19.0 x 8.0 in. (42.9 x 482.6 x 203.2 mm)
Dimensions (H x W x D)
Horizontal
Mounting style
10 ft (3.04 m)
Cable length
NEMA L6-30P
Plug
5.76
Maximum kW
200 to 240 V
Input voltage
200 to 240 V
Output voltage
24 A
Amperage
Single phase
Phase
50 to 60 Hz
Frequency
2 two-pole 20 A
Circuit breakers
8 IEC 60320 C13 outlets with outlet grip
4 IEC 60320 C19 outlets with outlet grip
Outlets
RS-232
Serial interface
10/100 Ethernet
Ethernet interface
Cisco R42612 Rack and RP-Series Metered Input PDU Installation Guide
50
Specifications
PDU Specifications