Step 4
Reset CIMC to Factory Defaults
For the 3160/3260: Log off the CIMC Management GUI and exit the CIMC GUI Management KVM console.
For the 3160:
a) Reboot server node and choose
<F8> Cisco IMC Configuration
to enter CIMC Configuration Utility
from the server node KVM connection.
b) Choose
<F1>Additional Settings
.
c) Down arrow to
FactoryDefaults[]
field.
d) Click the
spacebar
so that there is a[X].
e) Choose
<F10>Save
.
For the 3260:
a) Reboot server node and choose
<F8> Cisco IMC Configuration
to enter CIMC Configuration Utility
from the server node KVM connection.
b) Choose
<F1>Additional Settings
.
c) Down arrow to
FactoryDefaults/Chassis Controller Configuration[]
field. (The Server Controller
Configuration can be ignored as all CMC/BMC IP address information will be reset to factory defaults
with the Chassis Controller Configuration option).
d) Click the
spacebar
so that there is a[X].
e) Choose
<F10>Save
.
Shipping the Rack
Shipping Guidelines
After you complete the testing of a preracked UCS system, prepare the rack for shipment by following these
guidelines:
• To reduce the possibility of equipment damage or personal injury, remove all of the equipment that is
not mechanically secured to the rack rails before shipment. The only Cisco UCS components that can
be shipped preracked are certified Cisco UCS components with supplemental hardware. See
Placement Guidelines, on page 62
for more information.
• Tool-less rail kits must be secured into the rack rails using screws.
• The cables that connect to the fabric interconnect chassis may be bundled and secured using Velcro straps
prior to shipping. Secure all data and power cables.
• Special shock pallets must be used to ship approved racks with preinstalled UCS components. These
pallets were designed and tested for approved racks. They are designed only for one-way shipping and
must not be reused after the integrated rack reaches its final destination.
• The original packing materials that come with approved racks can be reused. These packaging materials
are designed for use with the approved racks.
• Carriers offering specialized, air-ride, padded vans are recommended for shipping all configured racks.
White glove service is encouraged and recommended.
Cisco R42612 Rack and RP-Series Metered Input PDU Installation Guide
83
Integrating UCS Components in the Dynamic Rack
Shipping the Rack