Firepower 7000 and 8000 Series Installation Guide
A P P E N D I X
A
Power Requirements for Firepower Devices
Warnings and Cautions
This document contains both warnings and cautions. Warnings are safety related. Failure to follow
warnings may lead to injury or equipment damage. Cautions are requirements for proper function.
Failure to follow cautions may result in improper operation.
Caution
The intra-building ports of the equipment or subassembly are suitable for connection to intra-building
or exposed wiring or cabling only. The intra-building ports of the equipment or subassembly
must not
be metallically connected to interfaces that connect outside the plant (OSP) or its wiring. These
interfaces are designed for use as intra-building interfaces only (Type 2 or Type 4 ports as described in
GR-1089-CORE, Issue 4) and require isolation from the exposed OSP cabling. The addition of the
primary protectors is not sufficient protection to connect these interfaces metallically to OSP wiring.
Static Control
Caution
Electrostatic discharge control procedures, such as using grounded wrist straps and an ESD work
surface, must be in place before unpacking, installing, or moving the appliance. Excessive electrostatic
discharges can damage the appliance or cause unintended operation.
Firepower 70xx Family Appliances
This section describes the power requirements for:
•
Firepower 7010, 7020, and 7030 (CHRY-1U-AC)
•
Firepower 7050 (NEME-1U-AC)
These appliances are suitable for installation by qualified personnel in network telecommunication
facilities and locations where the National Electric Code applies. Note that each is available only as an
AC appliance.
Cisco recommends that you save the packing materials in case a return is necessary.
For more information, see the following sections: