Figure 29: Replacing DC Power Supplies
PSU status LED
3
Keyed cable connector
(CAB-48DC-40A-8AWG)
1
-
Keyed DC input socket
2
Installing DC Power Supplies (First Time Installation)
This procedure is for installing DC power supplies to the server for the first time. If you are replacing DC
power supplies in a server that already has DC power supplies installed, see
.
Note
A readily accessible two-poled disconnect device must be incorporated in the fixed wiring.
Statement 1022
Warning
This product requires short-circuit (overcurrent) protection, to be provided as part of the building
installation. Install only in accordance with national and local wiring regulations.
Statement 1045
Warning
Installation of the equipment must comply with local and national electrical codes.
Statement 1074
Warning
Do not mix power supply types or wattages in the server. Both power supplies must be identical.
Note
Maintaining the Server
54
Maintaining the Server
Installing DC Power Supplies (First Time Installation)