Chapter 3 Installing the Wide Area Virtualization Engine
Installing the WAVE Appliance in an Equipment Rack
3-6
Cisco Wide Area Virtualization Engine 274 and 474 Hardware Installation Guide
OL-17739-01
Caution
Install the appliance only in a rack cabinet with perforated doors.
Rack Requirements
Install your WAVE appliance in a rack that meets the following requirements:
•
Minimum depth of 2.76 inches (70 mm) between the front mounting flange
and inside of the front door.
•
Minimum depth of 6.18 inches (157 mm) between the rear mounting flange
and inside of the rear door.
•
Minimum depth of 28.27 inches (718 mm) and maximum depth of 30 inches
(762 mm) between the front and rear mounting flanges to support the use of
the cable-management arm.
Racks are marked in vertical increments of 1.75 inches (4.44 cm). Each increment
is referred to as a rack unit (RU). A 1-RU device is 1.75 inches (4.44 cm) tall.
Rack Installation
To install the WAVE appliance in an equipment rack, follow these steps:
Step 1
Power down the appliance before beginning the installation.
Step 2
Attach shelf to rack rails with mounting hardware as shown in
Figure 3-4
.