Replacing the Power Supply
Installing the 3000 W AC-Input Power Supply
Caution
Use both hands to install and remove power supplies. Each Catalyst 6500 series AC-input power supply
weighs between 22 pounds (9.9 kg) and 28 pounds (12.6 kg).
To install the 3000 W AC-input power supply, follow these steps:
Step 1
Ensure that the system (earth) ground connection has been made. For ground connection instructions,
refer to the installation guide for your hardware platform.
Step 2
Verify that the power switch is in the Off (0) position on the power supply you are installing.
(See
Figure 7
.)
Figure 7
3000 Watt AC-Input Power Supply Front Panel
Step 3
Grasp the power supply handle with one hand. Place your other hand underneath the power supply, as
shown in
Figure 8
. Slide the power supply into the power supply bay. Make sure that the power supply
is fully seated in the bay.
INPUT
OK
FAN
OK
OUTPUT
FAIL
OUTPUT 42V /17A
42V /17A
OK
I
IN
ST
AL
L
RU
N
O
110-120V - 15A
200-240V - 15A
60/50HZ
+
105069
Power
switch
Cable
etention
device
AC power
connection
Captive installation
screw
Status LEDs (3)
External power
connector cover