Page 26
Dryer Installation with Separate Exhaust (Preferred)
For ductwork less than 14 feet (5 m) and 2 elbows equivalent and less than
0.3 inches (.8 mbar) static pressure.
NEVER exhaust the dryer into a chimney.
NEVER install wire mesh screen over the exhaust or
make-up air area.
NEVER exhaust into a wall, ceiling, or concealed space.
1. Make-Up Air opening from outside the building may enter the
enclosure from the top or side walls.
(See Dryer Make-up Air
Requirements Chart)
2. Enclosure (plenum) with service door. This separates the dryer
air from the room comfort air. If dryers use room air instead of
outside air, additional heat loss can be another 25 Btu/h
(6.3 kcal/h) for each cubic foot per minute (cfm) used.
3. Zero inches clearance to combustible material allowed on sides
and at points within 4 inches (102 mm) of front on top.
4. Heat loss into laundry room from dryer front panels is about
60 Btu/h (16 kcal/h) per square foot.
DRYER INSTALLATION
WITH SEPARATE
EXHAUST (PREFERRED)
Summary of Contents for HD150.1
Page 10: ...Page 10 150 lb Gas Fired Dryer Illustration ...
Page 13: ...Page 13 Gas Piping Installation Illustration ...
Page 15: ...Page 15 150 lb Steam Heated Models Illustration ...
Page 22: ...Page 22 Dryer Installation with Multiple Exhaust Illustration ...
Page 30: ...Page 30 Two Timer Models Figures 1 2 and 3 Illustrations ...
Page 38: ...Page 38 DIRECT SPARK IGNITION OPERATION FLOW CHART ...
Page 42: ...Page 42 Basket Alignment for 150 lb Dryers Illustrations ...
Page 44: ...Page 44 Shimming the Basket and Spider Assembly Illustration ...
Page 67: ...Page 67 ...