14 

5. OPERATION 

5.1 Check Prior to Start Up 

1. Ensure the UPS is in a suitable positioning. 

2. Check input cord is secured.   

3. Make sure the load is disconnected or in the “OFF” position. 

4. Check if input voltage meets the UPS rating required. 

5.2 Operation Procedure 

Please follow the instructions below for the UPS operation. 

1. Once the AC source is connected, the 

LCD Display shall light up immediately 

to display first the main menu of 

greeting context and the Normal LED is 

blinking to indicate ready to switch on 

the inverter.   

2. By pressing the UPS on/off Control Key and the LCD Select Down-key 

simultaneously for 3 seconds until the buzzer beeps twice, the UPS will 

start up and Normal LED lights up to indicate the power is from its inverter 

to the load. 

3. When the UPS on/off Control Key and the LCD Select Up-key are pressed 

simultaneously for 3 seconds until the buzzer beeps twice, the inverter will 

be turned off and the UPS is on the standby status (LCD display illuminates 

and Normal LED is blinking) until AC source is disconnected. 

5.3 Storage Instruction 

Disconnect input power in rear panel if you will not use it for long period. If the 

UPS is stored over 3 months, please keep supplying power to the UPS for at 

least 24 hours to ensure battery fully recharged.

 

15

5.4 LCD Display 

Use Up/Down key to select menu-displays of the LCD described below. This 

screen will refresh once the system power is enabled. 

1. Rated Spec Menu 

 

2. Status Menu 

 

3. Voltage Menu 

 

 

 

4. Frequency Menu 

 

 

 

Summary of Contents for CPO-S1000

Page 1: ...O S1000R CPO S2000R CPO S3000R Uninterruptible Power Supply 1 CONTENTS 1 INTRODUCTION 1 2 SAFTY INSTRUCTION 2 3 SYSTEM DESCRIPTION 4 4 CABLE CONNECTION 7 5 OPERATION 8 6 TROUBLE SHOOTING GUIDE 13 7 OP...

Page 2: ...er 4 If the UPS will be stored for long period the battery must be charged once every 90 days 5 Retain the load within the rating of UPS to prevent faults 6 Handle unusual events according to the trou...

Page 3: ...nt Please take the precautionary measures specified below and any other measures necessary when working with batteries remove wristwatches rings and other metal objects use only tools with insulated g...

Page 4: ...shutdown or over temperature 6 Warning LED yellow To indicate the UPS is in the status of overload bypass and battery back up 7 Normal LED green To indicate the UPS is operating normally 3 2 Outline D...

Page 5: ...9 RS 232 Interface Port 6 Remote Control Mini LCD for LED panel only Option 2 SNMP Intelligent Slot Option 7 Fan 3 Fax Modem Surge Protection 8 External Battery Socket 4 Remote Control Detachable LCD...

Page 6: ...ker 5 External Battery Socket 10 Output Socket NEMA or IEC 11 2KVA 3KVA Tower Case 1 DB 9 RS 232 Interface Port 7 External Battery Socket 2 SNMP Intelligent Slot Option 8 Remote Control Mini LCD for L...

Page 7: ...e the nominal amperage of your incoming feeder 3 Inspect the packaging carton and its contents for damage Please inform the transport agency immediately should you find signs of damage Please keep the...

Page 8: ...beeps twice the UPS will start up and Normal LED lights up to indicate the power is from its inverter to the load 3 When the UPS on off Control Key and the LCD Select Up key are pressed simultaneousl...

Page 9: ...and HI high In this screen press on off Control Key to enter the following steps for LO HI voltage setting B The cursor will pop up to indicate the item newly selected Press on off Control Key to get...

Page 10: ...ING GUIDE 6 1 UPS Status and Action The description of the following guideline may be helpful in problem solving 1 LED and LCD status as below UPS STATUS AC utility power is normal UPS is running norm...

Page 11: ...LED and LCD status as below UPS STATUS AC utility power is normal but the load is supplied by AC utility power via bypass Output power is more than 150 referring to the Output Power Menu Warning LED...

Page 12: ...ill restart up when AC utility power is restored If AC utility power failure is more than 6 hours please follow storage instruction 23 7 OPERATION MODES OF THE UPS 7 1 UPS System Block Diagram 7 2 Nor...

Page 13: ...o communicate with the computer Its major functions are as follows 1 To broadcast a warning when power fails 2 To close any open files before the battery exhausted out 3 To turn off the UPS 2 Supply R...

Page 14: ...d discharge Transfer Time AC fail 0 ms 2 5ms typical from inverter to bypass and vice versa Battery Battery low shutdown and Fuse Overload 125 150 30sec then switch to bypass and auto re transfer 150...

Page 15: ...76V 253V 20V re settable via LCD panel Transfer Time AC fail 0 ms 2 5ms typical from inverter to bypass and vice versa Battery Mode Beeping every 4 seconds re settable and per second when battery low...