background image

DCN: 2012-11-222-1                                                                                                                                             Page 1 

 

 

Installation Guide     

Model CH-THSTAT-W 

 

This thermostat is compatible with most HVAC systems, including the following: 
 

 

24VAC systems  

Note: requires both the 24R and 24C (common) wires

 

 

Standard gas/oil/electric heating systems   

o

 

1 stage heating and cooling 

o

 

2 stage heating and cooling 

 

Heat Pump systems: 

o

 

1 stage heating and cooling 

o

 

2 stage heating and cooling 

o

 

2

nd

 or 3

rd

 stage Auxiliary heating (heat strips)  

 

Do NOT use for line voltage controls (120/240VAC) 

 
Stop!  Before removing your existing thermostat be sure to label the wires with the wiring 
labels included.  Label the wires as they were 

connected to the old thermostat terminals

 

and record them below.   

 

We strongly recommend you 

take a picture of your existing thermostat wiring

 

connections. This will enable you to reconnect your old thermostat if you encounter a 
problem installing the CH-THSTAT-W and will assist in trouble shooting the installation, if 
needed. 

 

CAUTION: The typical wire colors noted below may be different from your installation. 

 

 

Standard HVAC System Wiring  

 

Thermostat 

Terminal Marking 

Meaning 

Typical Wire 

Color 

Record the 

old thermostat

 wire color 

connected to this terminal here 

C                         

24VAC Common     

Blue 

 

R (or RH)                        

24VAC Return (heating system) 

Red 

 

G                        

Fan 

Green 

 

W or W1             

Heat stage 1 

White 

 

Y or Y1               

Cool stage 1 

Yellow 

 

W2                     

Heat stage 2 

Orange 

 

Y2                      

Cool stage 2 

Black 

 

 

Heat Pump HVAC System Wiring 

 

Thermostat 

Terminal Marking 

Meaning 

Typical Wire 

Color 

Record the 

old thermostat

 wire color connected 

to this 
terminal here 

C                         

24VAC Common     

Blue 

 

R                         

24VAC Return 

Red 

 

G                        

Fan 

Green 

 

W or W1             

Aux Heat 

White 

 

Y or Y1               

Compressor stage 1 

Yellow 

 

O  (or B*)                

Change Over Valve 

Orange 

(brown*) 

 

Y2                      

Compressor stage 2 

Black 

 

 

* if you have a terminal marked “B” with a brown wire attached to it, that means you have a changeover (C/O) with heating 
type heat pump system.  Be sure to set the change over type in the 

Installer Settings

 menu to 

C/O Type:  w/Heat.  

Otherwise leave it set to 

w/Cool

Summary of Contents for CH-THSTAT-W

Page 1: ...THSTAT W and will assist in trouble shooting the installation if needed CAUTION The typical wire colors noted below may be different from your installation Standard HVAC System Wiring Thermostat Term...

Page 2: ...TW45 Ver 02 04 01 WiFi Radio Version 02 30 System Type Standard Fan Type Gas Network Address 1 Status Press the MENU button to go to the main menu screen Scroll down to the Thermostat Info using down...

Page 3: ...Elec Fan Type Gas 2nd Stage Heat N 2nd Stage Cool N Done If HVAC system is a Standard Gas or Electric heat system Set the Type Standard Gas Electric systems or HP systems Set the Fan Type Gas or Elect...

Page 4: ...on a live system Network Settings Submenu Shows WiFi settings Same as in the Main Menu selection See Operations Manual System Settings Submenu Sets the HVAC operational settings below Mechanical Setti...

Page 5: ...at stage 1 heating starts Heating Delta Stage 1 OFF Range 0 to 8 degrees Default 0 Sets the delta from setpoint that stage 1 heating stops Stage 1 turns off at setpoint Delta Stage 1 Heating Delta Sta...

Page 6: ...g cooling cycle can begin Provides compressor short cycle protection Fan Cycler The fan cycler function cycles the HVAC system fan for an ON period followed by an Off period continuously Used to provi...

Page 7: ...1 On 1 8 1 Cool Delta Stage 1 Off 0 8 0 Cool Delta Stage 2 On 1 8 2 Cool Delta Stage 2 Off 0 8 0 Max Heat SP 40 109F 4 42C 90F Min Cool SP 44 113F 6 45C 60F Min Run Time 1 9 min 3 Min Off Time 1 9 mi...

Page 8: ...o Elec for electric heat fan call with heat call 3 2nd Stage Heat Enable second stage heating outputs If you have a single stage heating system leave this set to N If you have a 2 stage heating system...

Page 9: ...the correct system operation For change over with cool systems Orange wire O terminal set C O type to w cool most common and default setting For change over with heat systems Brown wire B terminal se...

Reviews: