Application

Use this filter to screen effluent under pressure.  The base screen will 

remove particles greater than 1/16" in diameter. An additional filter 

sock will screen to either 100 or 600 microns. Applications include 

LPP, sand filters, pressure dosed wetlands, drip distribution, and most 

pressure applications.

Installation

Determine the discharge pipe length needed from pump to filter. Install 

a 2" PVC discharge pipe for the 5000-0001 or a 3" PVC discharge pipe 

for the 5000-0008. Note: Pumps with a smaller discharge size may be 

adapted to fit. Glue the filter to the end of the discharge pipe. Glue a 

6” long PVC pipe to a PVC union ball valve and glue this assembly to 

the discharge of the filter. Plumb the discharge into the union and glue. 

NOTE: Use PVC primer and solvent on all glue joints.

Service

The Clarus Environmental Pressure Effluent Filter requires periodic 

service. The optional Service Alarm Switch will indicate when service 

is needed. Excessive pump run times or high water may also indicate 

a clogged filter. At a minimum, service the filter each time the septic 

tank and/or pump chamber is serviced. Check with your local health 

department for pumping recommendations.

To service the filter screen, disconnect power to the pump and unscrew 

the 4" lid. Pull the filter screen from the housing and wash it out thoroughly 

in an appropriate location with proper protection. Reinsert the cleaned 

filter screen, replace the 4" lid and restore power to the pump. For 

service providers, a spare screen will allow for a faster service visit, 

since the dirty filter can simply be replaced and cleaned later at the 

service provider’s convenience.

If the system is equipped with our Service Alarm Switch, the filter screen 

does not need service until the Service Alarm Switch activates a light 

or audio alarm.  Service is still recommended each time the septic tank 

and/or pump chamber is serviced.

Sock Installation

To  install  the  sock  in  a  standard  filter  screen,  remove  the 

 

1/16" diameter SS wire handle by straightening out the 90° bend in 

the wire handle with pliers and removing it from the filter screen. The 

sock is installed inside of the filter screen.

At this time, the sock can be placed inside the canister screen and 

wrapped around the seating surfaces on the top and bottom. This will 

secure the sock in the filter. The sock is a 100 micron thermal nylon 

or 600 micron seamless knitted polyester with 100 psi burst strength. 

The sock is several inches longer than the filter screen so as to allow 

the sock to be pulled around the filter screen flanges and secured as 

shown below.

         LID W/SEAL

FILTER HOUSING

FILTER SCREEN

OPTIONAL SOCK

INSTALLATION

SK2208A

Pressure Effluent Filter 

SECTION: C2.30.130

CL0050

0515

Supersedes

1011

3649 Cane Run Road  Louisville, KY 40211-1961

800-928-7867  Fax:  502-774-3624

www.clarusenvironmental.com

®

®

OWNER'S MANUAL

Register your 

Clarus Environmental Product 

on our website:

http://reg.clarusenvironmental.com/

Reviews: