T H E C O N T I N U O U S P O W E R C O M P A N Y
Page 32
OPT_TRAFFIC: (Enter Hex value)
OPT_TRAFFIC =1
=0
Bit 7 (MSB)
Long return always
Short return
6
Long return if Flash volt or
minute triggers occurred.
Short return
5
SIGNAL port pin 2 carries
Flash Timeout Trigger.
SIGNAL port pin 2 carries
Utility Fail indication.
4 Brownout
Protection
Disabled
Brownout Protection
Enabled
3 Reserved
Fixed
0
2 Reserved
Fixed
0
1
Bypass Disabled
Bypass Enabled
0
Bypass Overloads
Don’t Bypass Overloads
Default: 30H
Notes:
•
Long returns insert 2.5 second power breaks upon return from
Standby
operation. Short returns add no breaks.
OPT_MISC: (Enter Hex value)
OPT_MISC =1
=0
Bit 7 (MSB)
Reserved
Fixed 0
6 Sets
Continuous
Operating
Mode
Sets
Standby
Operating
Mode
5 Reserved
Fixed
0
4 Reserved
Fixed
0
3 Reserved
Fixed
0
2
Battery Test enabled
Battery Test disabled
1
UPS output synched to
utility.
Un-synched output
0 Fixed
1
Reserved.
Default: 06H
Notes:
•
Standby