BACKUP DELAY (x10 msec)
This value sets the time period of the utility AC noise rejection window. Utility
disturbances of duration less than this setting are ignored. Units are in 10msec. For
example, 40 millisecond delay is specified by 4.
Default: 4
Range: 1 – 100
Notes: Feature cannot be disabled.
FLASH TRIGGER (Volts)
Enter this value in decimal units of volts. This is the voltage specifies the trip point that
activates the Flash operation via the “LOW-BATT” relay contacts in the PIM.
Default: 69
Range: 0 – 90V
Notes: 0 Disables feature
FLASH TRIGGER (Minutes)
Enter this value in decimal units of minutes. This is the voltage specifies the trip point
that activates the Flash operation via the “TIMER” relay contacts in the PIM.
Default: 120
Range: 0 – 255 minutes
Notes: 0 Disables feature