T H E C O N T I N U O U S P O W E R C O M P A N Y
Page 42
7. The rechargeable battery is recyclable. At the end of its useful life, under various
state and local laws, it may be illegal to dispose of this battery into the municipal
waste stream. Check with the factory for details in your area for recycling options or
proper disposal.
BATTERY RECYCLING
•
The batteries used in this equipment are recyclable. Proper disposal is required and
mandated by law. The batteries contain lead and pose a hazard to the environment
and human health if not dispose of properly.
•
Refer to local codes for proper disposal requirements or return the batteries to the
factory.
•
ALWAYS contact the factory for information concerning shipment, disposal, or
replacement of batteries.
Table 11: PREVENTIVE MAINTENANCE SCHEDULE
Item Schedule
Actions
Cleaning
6 Mos.
Blow out unit with air.
Battery
6 Mos.
Clean terminals and check for corrosion.
5.3 TROUBLE
ANALYSIS
Unit does not power up:
•
Make sure AC & DC input connectors are connected and seated properly.
•
Check front panel fuse(F1)
•
Check PIM for proper installation and wiring.
Battery LED’s on front panel is flashing:
•
Make sure when you power up the unit, turn DC breaker on first, then turn on the
system switch.
No Backup when utility power is lost:
•
Make sure DC breaker is in the “ON” position.
•
If Bypass switch is installed, make sure it is in the “UPS” position.
•
Check PIM for proper installation and wiring.
•
Possible Bad PIM.
•
Check
Batteries.