TROUBLESHOOTING AND REPAIR

Anomalies

Causes and repairs

The generator does not start 

(red light is off)

Make sure that:

- the electrical connection is correct

- If a room thermostat is installed, check that it is not set below the 

room temperature.

The fan does not work (red 

light is off)

Check :

- the motor power cable; 

- the F1 protection fuse

- the fuel pump; if it is seized, it must be replaced.

The fan comes on but there 

is no combustion (after a few 

seconds the RESET button 

lights up)

- Check the fuel level; 

- Check that the fuel filter is not clogged;

- Check that the nozzle is not clogged;

- Check that there is no air in the fuel system:

Make sure that the glass ball of the fuel filter is properly screwed in and 

that the O-ring seal is properly positioned in its seat.

- The photocell is dirty: remove it from its support and clean it.

- Check that the plastic seal between the motor and the fuel pump is in 

good condition: if it is broken, it must be replaced.

- The combustion control box is defective: replace it.

- Check whether there is a spark between the electrodes. If not, check 

position and

If not, check the position and condition of the electrodes and high 

voltage cables. Check if the transformer is burned.

The device overheats during 

use

- Fuel flow is too high due to nozzle wear or normal operation. Use of a 

nozzle with different characteristics than the original.

- Combustion air flow is too low due to incorrect adjustment of the 

combustion head fins.

- Obstructions in the ventilation air path.

When the unit is switched off 

by 

or the room thermostat, the 

fan does not start and the 

generator overheats.

and the generator will 

overheat.

- The cooling thermostat is defective.

It must be replaced.

The device emits white smoke

- Excessive combustion air or poor quality fuel.

- Impurities in fuel; clean tank, glass and lines. Replace fuel.

- Air setting has been changed; reset fins to original position.

The device emits black smoke

- Too little combustion air or too much fuel flow due to

due to :

- Nozzle is out of adjustment or not in compliance: replace;

- Incorrect fuel pressure;

- Deflector disk is clogged: clean.

- Incorrect air setting: reset the fins to their original position.

Summary of Contents for CH 0022

Page 1: ...CH 0022 CHAUFFAGE FIOUL DIRECT 20kw DIRECT DIESEL OIL HEATER 20kw CH 0023 CHAUFFAGE FIOUL DIRECT 30kw DIRECT DIESEL OIL HEATER 30kw CH 0024 CHAUFFAGE FIOUL DIRECT 40kw DIRECT DIESEL OIL HEATER 40kw CH...

Page 2: ...sur notre site clas com Si vous avez chang d avis concernant votre achat veuillez retourner ce produit avant d essayer de l installer Before returning this product for any reason installation problem...

Page 3: ...14 197 16 5 500 1 39 Diesel Kerosene 20 100 230 50 79x27x50 21 CH 0023 17 200 20 500 1 66 20 100 230 50 79x27x50 24 CH 0024 25 800 30 1 750 2 53 35 150 230 50 125x55x65 44 CH 0025 34 400 40 1 750 3 3...

Page 4: ...4 CH 0022 CH 0023 CH 0024 CH 0025 CH 0026 SCHEMAS ELECTRIQUES P Pompe S Appareillage EV Electrosoupape F Fusible C Interrupteur M Moteur SR Sonde TL Thermostat TA Thermostat ambiant...

Page 5: ...CHAUFFAGE FIOUL DIRECT 16 5kw 20kw 30kw 40kw 50kw 5 VUE CLAT E T te de combustion Porte buse Capsule de t te lectrodes...

Page 6: ...6 CH 0022 CH 0023 CH 0024 CH 0025 CH 0026 Porte buse...

Page 7: ...CHAUFFAGE FIOUL DIRECT 16 5kw 20kw 30kw 40kw 50kw 7 T te de combustion...

Page 8: ...ces salles les g n rateurs directs ne doivent tre utilis s que pour s cher les salles si l on garantit la quantit d air n cessaire pour la combustion vous obtenez la quantit d air n cessaire quand la...

Page 9: ...re installer par un lectricien qualifi un disjoncteur diff rentiel haute sensibilit intervention 30 mA ou inf rieure En cas de n cessit il est possible d utiliser des rallonges du c ble d alimentation...

Page 10: ...la partie int rieure de la t te de combustion s enl ve il reste seulement le corps cylindrique et l embout conique accessible pour le nettoyage N B Pendant le remontage de la t te apr s avoir effectu...

Page 11: ...ion est d fectueuse remplacer S assurer si une tincelle se produit entre les lectrodes Dans le cas contraire v rifier la position et le bon tat des lectrodes et des c bles haute tension V rifier si le...

Page 12: ...6 5 500 1 39 Diesel Kerosene 20 100 230 50 79x27x50 21 CH 0023 17 200 20 500 1 66 20 100 230 50 79x27x50 24 CH 0024 25 800 30 1 750 2 53 35 150 230 50 125x55x65 44 CH 0025 34 400 40 1 750 3 37 35 150...

Page 13: ...13 DIRECT DIESEL OIL HEATER 16 5kw 20kw 30kw 40kw 50kw ELECTRICAL DIAGRAMS P Pump S Equipment EV Electrovalve F Fuse C Switch M Motor SR Probe TL Thermostat TA Ambient thermostat...

Page 14: ...14 CH 0022 CH 0023 CH 0024 CH 0025 CH 0026 EXPLODED VIEW Combustion head Porte buse nozzle holder capsule de t te head cap electrodes...

Page 15: ...15 DIRECT DIESEL OIL HEATER 16 5kw 20kw 30kw 40kw 50kw Nozzle holder...

Page 16: ...16 CH 0022 CH 0023 CH 0024 CH 0025 CH 0026 Combustion head...

Page 17: ...the entrance must prohibit the permanent presence of people in these rooms direct generators should only be used to dry rooms if the necessary amount of air for combustion is guaranteed you get the n...

Page 18: ...vity differential circuit breaker intervention at 30 mA or less If necessary it is possible to use extension cables with a cross section of 1 5 mm2 for lengths up to 10 m and 2 5 mm2 for lengths betwe...

Page 19: ...letely removed Unscrew the 2 screws the entire inner part of the combustion head is removed leaving only the cylindrical body and the conical end accessible for cleaning N B When reassembling the head...

Page 20: ...ustion control box is defective replace it Check whether there is a spark between the electrodes If not check position and If not check the position and condition of the electrodes and high voltage ca...

Page 21: ...21...

Page 22: ...22...

Page 23: ...23...

Page 24: ...24...

Page 25: ...25...

Page 26: ......

Page 27: ......

Page 28: ...zed technician CLAS Equipements 83 chemin de la CROUZA 73800 CHIGNIN FRANCE T l 33 0 4 79 72 62 22 Fax 33 0 4 79 72 52 86 CH 0026 CHAUFFAGE FIOUL DIRECT 30kw DIRECT DIESEL OIL HEATER 30kw CHAUFFAGE FI...

Reviews: