26
8.3 Main Protection
8.3.1 Three minutes delay at restart for compressor
1 minute delay for the 1
st
time stand-up and 3 minutes delay for others.
8.3.2 Temperature protection of compressor top
The unit will stop working when the compressor top temp. protector cut off, and will restart after the
compressor top temp. protector restart.
8.3.3 Temperature protection of compressor discharge
When the compressor discharge temp. is getting higher, the running frequency will be limited as below
rules:
---Compressor discharge temp. T5>115°C(239°F) for 5s, compressor stops.
---108°C (226°F)<T5<115°C(239°F), decrease the frequency to the lower level every 3 minutes.
---90°C(194°F)<T5<105°C(221°F), keep running at the current frequency.
----T5<90°C(194°F), no limit for frequency.
8.3.4 Fan speed is out of control
When Indoor fan speed keeps too low (300RPM) for certain time, the unit will stop and the LED will
display the failure
8.3.5 Inverter module protection
The Inverter module has a protection function about current, voltage and temperature. If these
protections happen, the corresponding code will display on indoor unit and the unit will stop working.
8.3.6 Indoor fan delayed open function
When the unit starts up, the louver will be active immediately and the indoor fan will open 10s later.
If the unit runs in heating mode, the indoor fan will be also controlled by anti-cold wind function.
8.3.7 Compressor preheating functions
Preheating permitting condition:
If T4(outdoor ambient temperature)
<
3°C(37.4°F) and the machine connects to power supply newly or
if T4
<
3°C(37.4°F) and compressor has stopped for over 3 hours, the compressor heating cable will
work.
Preheating mode:
A weak current flow through the coil of compressor from the wiring terminal of the compressor, then the
compressor is heated without operation.
Preheating release condition:
If T4
>
5°C(41°F) or the compressor starts running, the preheating function will stop.
8.3.8 Zero crossing detection error protection
If AC detects time interval is not correct for continuous 240s, the unit will stop and the LED will display
the failure. The correct zero crossing signal time interval should be between 6-13ms.
8.3.9 Condenser temperature protection
---55°C(131°F)<T3<60°C(140°F), the compressor frequency will decrease to the lower level until to F1
and then runs at F1.If T3<54°C(129.2°F), the compressor will keep running at the current frequency.
---T3<52°C(125.6°F), the compressor will not limit the frequency and resume to the former frequency.
---T3>60°C(140°F) for 5 seconds, the compressor will stop until T3<52°C(125.6°F).
8.3.10 Evaporator temperature protection
---T2<0°C(32°F), the compressor will stop and restart when T2
≧
5°C(41°F).
---0°C(32°F)
≦
T2<4°C(39.2°F), the compressor frequency will be limited and decreased to the lower
level
---4°C(39.2°F)≤T2≤7°C(44.6°F), the compressor will keep the current frequency.
Summary of Contents for MROHC09AS
Page 14: ...12 5 Wiring Diagram 5 1 Indoor Unit MWOHC09S MWOHC12S MWOHC18S ...
Page 15: ...13 MWOHC24S ...
Page 16: ...14 5 2 Outdoor Unit MROHC09AS MROHC12AS ...
Page 17: ...15 MROHC18AS ...
Page 18: ...16 MROHC24AS MROHC09AS MROHC12AS ...
Page 19: ...17 MROHC18AS ...
Page 29: ...27 T2 7 C 44 6 F the compressor frequency will not be limited ...
Page 53: ...51 Take the 9k model as example P V P U ...
Page 54: ...52 N U P W ...
Page 55: ...53 N W N V ...