29
Note:
When T1-Ts keeps in the same temp. zone for
3 minutes, the compressor will run as the below
rules:
A~E: Increase the frequency to the higher level
until to F8.
F: Keep the current frequency.
G: Decrease the frequency to the lower level
until to F1.
H: Run at F1 for 1h.(if T1-Ts<-2°C(28.4°F), the
compressor will stop)
Meanwhile, the compressor running frequency
is limited by the current.
I3COOL
I2COOL
I1COOL
I3COOL, I2COOL,I1COOL mean different
running current value.
Off: Compressor stops.
Decrease: Decrease the running frequency to
the lower level.
Hold: Keep the current frequency.
Resume: No limitation for frequency.
Note:
When AC is in “hold” zone for 3 minutes, the
compressor frequency will rise to the higher
level.(frequency will increase twice at most)
T4
28¡ãC(82.4¡ãF)
26¡ãC(78.8¡ãF)
22¡ãC(71.6¡ãF)
20¡ãC(68.0¡ãF)
8.4.2.3 Indoor fan running rules
In cooling mode, indoor fan runs all the time
and the speed can be selected as high,
medium, low, auto and silent mode. When the
compressor is running, the indoor fan is
controlled as below:
For MWOHC09S, MWOHC12S,
MWOHC18S models:
Auto fan running rules:
For MWOHC09S, MWOHC12S,
MWOHC18S models:
T1-Ts
8.4.2.2 Outdoor fan running rules
6.0¡ãC(42.8¡ãF)
5.0¡ãC(41.0¡ãF)
4.0¡ãC(39.2¡ãF)
2.5¡ãC(36.5¡ãF)
1.0¡ãC(33.8¡ãF)
H
(H-L)*0.75+L
(H-L)*0.5+L
(H-L)*0.25+L
L
Off
Decrease
Hold
Resume
H
M
L
b
c
a
d
e
Summary of Contents for MROHC09AS
Page 14: ...12 5 Wiring Diagram 5 1 Indoor Unit MWOHC09S MWOHC12S MWOHC18S ...
Page 15: ...13 MWOHC24S ...
Page 16: ...14 5 2 Outdoor Unit MROHC09AS MROHC12AS ...
Page 17: ...15 MROHC18AS ...
Page 18: ...16 MROHC24AS MROHC09AS MROHC12AS ...
Page 19: ...17 MROHC18AS ...
Page 29: ...27 T2 7 C 44 6 F the compressor frequency will not be limited ...
Page 53: ...51 Take the 9k model as example P V P U ...
Page 54: ...52 N U P W ...
Page 55: ...53 N W N V ...