connector posts on the PEM. Set the nuts and washers aside.
10. Connect the power-feed cables (with Panduit connector P/N LCAX8-14-L or equivalent) to
the appropriate connectors. Check the labels next to the connectors for polarity.
11. Reattach the removed nuts and washers. Torque the nuts to 6.95 Nm (61.5 lbf-in).
12. Reattach the safety cover. Torque the safety cover screw to 0.90 Nm (8 lbf-in).
13. Turn on the power distribution to the power-feed cables.
Turning On Power
In the following steps, a loud alarm may sound if an alarm condition occurs and the chassis has
the alarm panel installed. Be prepared to insert the end of a pen or a paperclip into the pinhole
labeled with the "alarm off" graphic (a bell with line through it) on the front panel to press the
button. This acknowledges and silences the alarm.
To power up the chassis:
1.
One at a time, switch the PEM circuit breakers to the ON position.
2.
Verify the power LEDs on the PEMs, the SFBs, and the other modules are all lit solid green.
3.
Wait for any automatic boot-up actions to occur. In particular, verify the hot-swap LEDs on
all the modules stop blinking. If any hot-swap LED continues to blink for more than two
minutes, verify the module is properly latched.
Chapter 7: Connecting Power
28