17
WARNING:
Codes may require that the furnace is mounted eight (8) feet above the
floor if there is potential for gasoline fumes. Refer to NFPA 88B, Standard for Repair
Garages.
Mounting the furnace in position:
HANGING THE FURNACE FROM THE CEILING:
(1) Refer to Figure 12 for a typical ceiling hung illustration.
(2) Remove the kerf cut holes in the corners of the top and bottom of the furnace cabinet.
(3) Insert all-thread rod (minimum 1/2”) through the cabinet and put a washer and two nuts
on the bottom.
(4) Use adequately sized square tubing or angle iron across sufficient structural members to
safely carry the weight of the furnace.
(5) Put a washer and two nuts on the top of each all-thread rod
(6) Use a level to ensure the furnace is hanging level front-to-back and side-to-side.
WARNING:
Use adequate structural members to safely bear the weight of the furnace
when either hanging it from the ceiling or mounting it on a stand.
Figure 12: Typical Ceiling Hung Furnace
FURNACE INSTALLATION
MINIMUM
1/2" ALL THREAD
ROD (4 Pieces)
DOUBLE NUTS
(4 Places)
DOUBLE NUTS
(4 Places)
USE ADEQUATE STRUCTURAL
MEMEBERS TO SAFELY BEAR
THE WEIGHT OF THE FURNACE
WARNING:
CE70166
Summary of Contents for CE-140