17
Oil storage tank setup:
Figure 12: Typical Oil Storage Tank Installation
(1) Refer to Figure 12 for a typical oil storage tank setup.
(2) The tank must be installed according to all NFPA requirements and State and Local codes.
(3) An inside tank is recommended.
(4) Locate the tank in a position that will allow the oil pump to be mounted as close as possible
(5) Only use a tank with a drain on the bottom. Over time, dirt and sludge will naturally
accumulate on the bottom of the tank and there must be a way of removing this unwanted
material.
(6) Some state and local codes require the tank to be vented to the outside.
(7) Educate all personnel what substances are allowed to be added to the used oil supply and
apply the provided tank warning label near the fill location.
Installing the metering pump system and oil lines:
Metering Pump Installation Guidelines:
(1) Use non-hardening thread sealer for all threaded pipe fittings. DO NOT use teflon tape.
(2) The pump must be installed with the shaft in the horizontal position and the oil outlet
pointing up.
NOTICE:
The gauge arrow on the front of the pump head must be pointing up.
CAUTION:
The metering pump must be mounted above the oil tank. The pump is
not designed to take head pressure. If the pump is below the level of oil in the tank the
pump seals may begin to leak.
BOILER INSTALLATION
8
FT
. MA
X
IMU
M L
IF
T
SUCTION
OIL LINE
8" MIN
RELIEF
RETURN
CE70024
PRESSURE
OIL LINE
PRESSURE OIL LINE TO
THE HEATING EQUIPMENT
EMERGENCY
VENT
DRAIN PAN
WITH SHUT OFF
VALVE
CHECK VALVE
CLEAN OUT
VALVE WITH
PLUG
SUCTION OIL LINE IS ONE CONTINUOUS
PIECE OF COPPER TUBING INSTALLED
THROUGH THE SLIP FITTING
VENT
CAP
Summary of Contents for CE-340
Page 2: ...7 3 13 Part 70006 Underwriters Laboratories File MH48829 ...
Page 35: ...BOILER DIMENSIONS 35 57 5 42 5 67 with Burner 34 0 CE70077 50 ...
Page 40: ...40 1 4 12 6 15 9 10 14 3 2 11 5 13 8 7 Nozzle Adapter Heater Block Assembly ...
Page 42: ...42 2 5 7 6 4 5 3 12 11 9 8 10 1 CE70058 CE 4 Manifold Block Assembly ...