background image

 

   

 

 

 

 

 

 

 

 

         

Maintenance

 (continued) 

16 

• 

Cover  Filter:  Check  the  cover  filter  element  mounted  on  the  side  of  the  air  preparation  system  and  clean  as 
required.  Operating  conditions  in  the  equipment  area  will  dictate  the  frequency  required  for  this  procedure. 
Remove the filter element and clean with soap and water, drying them completely before re-installing.

 

Ozone Generator 

• 

Drive  Module  Operation:  The  Drive  Module  is  made  up  of  two  components:  the  drive  board  and  the  drive 
transformer. With the ozone generator cover removed, check for illumination of the drive module "Ozone Output" 
LED(s)  (for  LED  locations,  see  Figure  8-1);  if  not  illuminated  see  Troubleshooting  Guide.  This  procedure  is  to 

observe

 the complete operating function of the drive module(s). Before checking drive module function, remove 

the  ozone  generator  cover  and  depress  the  cover  safety  switch  located  on  the  ozone  generator  chassis  (see 
Appendix, Section A). 

CAUTION: This overrides the cover safety switch. The ozone generator will remain 

energized  with  the  cover  removed.  Do  not  touch  anything  inside  the  ozone  generator  while  this  switch  is 
activated!

 

Please consult your ClearWater Tech dealer before attempting this procedure.

 

-  Main  Power  LED:  When  illuminated,  this  “Green”  LED  indicates  that  main  power  is  supplied  to  the  drive 

module up to the “on board” fuse of the drive board. 

-  Transformer Power LED: When illuminated, this “Green” LED indicates that 48V Buss power is available to 

the drive module transformer (XFMR) from the “on board” fuse of the to the drive transformer. 

-  Ozone  Output  LED:    The  “Amber”  ozone  output  LED  will  illuminate  when  ozone  drive  is  being  generated.  

The  LED  will  also  pulse  as  the  output  increases  or  decreases  with  either  the  Manual  Ozone  Output  Control 
located on the bottom of the ozone generator (see Appendix, Section A), or from a Remote 4-20mA signal (see 
“Installation Procedures – Electrical”).  

-  Fault  LED:  When  illuminated,  this  “Red”  LED  indicates  that  there  is  a  fault  with  the  drive  module  or  the 

Ozone Reaction Chamber. If this LED is illuminated, refer to the Troubleshooting Guide.  

Notes: If the drive 

module  goes  to  a  fault  condition,  the  drive  board  will  restart  every  30  seconds.  If  the  fault  is  not 
remedied the drive module will continue to go into a fault mode. When the drive module is in fault mode 
ozone will not be generated.  Before proceeding further, release the cover safety switch and replace the 
ozone generator cover. 

 

• 

Cooling  Fan  Operation:  Check  to  make  sure  the  two  cooling  fans  (mounted  on  the  bottom  panel  of  the  ozone 
generator cabinet) are operating. If not, refer to the Troubleshooting Guide. 

 

• 

Cooling  Fan  Filters:  Check  the  cooling  fan  filter  elements  mounted  on  the  bottom  of  the  ozone  generator  (see 
Appendix, Section A) and clean as required. Operating conditions in the equipment area will dictate the frequency 
required  for  this  procedure.  Remove  the  filter  element  and  clean  with  soap  and  water,  drying  them  completely 
before re-installing (see Figure 8-2). 

Booster Pump(s) 

• 

Strainer Baskets: Check and clean the strainer basket in the booster pump(s) as required (if so equipped)

 

Drive Module High Output (H.O.)  
 
 

Figure 8-1

 

 

 

 

 

 

  

 

Transformers – XFMR (under 

boards) 

 

Drive Board 

 

Ozone Output LED 

 

Fuse 

 

Transformer – XFMR LED 

 

Drive Board Main Power LED 

 

Fault LED 

 

24VDC Output Connector 

 

Variable Input Connector 

 

DC Power Input Connector 

Summary of Contents for CD1500P

Page 1: ...s a component only Tested and certified by WQA to NSF ANSI 50 as a component only ClearWater Tech LLC Integrated Ozone Systems 850 E Capitolio Way San Luis Obispo Ca 93401 805 549 9724 Fax 805 549 030...

Page 2: ...o achieve the ozone output and longevity of the ozone generator A pounds per square inch PSI regulator must be installed when using plant air feed gas This regulator must be set to a maximum of 10 PSI...

Page 3: ...m of extremely tiny bubbles These bubbles must be as small as possible in order to increase the ratio of bubble surface area to the amount of ozone entering the water Depending on the application and...

Page 4: ...s detectable at very low concentrations 0 02 ppm which is far below OSHA s maximum permissible exposure level of 0 1 ppm HIGH VOLTAGE WARNING CLEARWATER TECH OZONE GENERATORS OPERATE AT HIGH VOLTAGE D...

Page 5: ...ipment 7 The electrical supply for this product must include a suitably rated switch or circuit breaker to open all ungrounded supply conductors to comply with Section 422 20 of the National Electrica...

Page 6: ...justment chemical injection point must be located downstream of the residual sanitizer injection point if so equipped In a Full Flow plumbing configuration see Figure 4 2 without recirculation locate...

Page 7: ...ical print or as dictated by equipment layout and serviceability considerations Do not secure booster pump and contact vessel to housekeeping pads at this point Dry fit plumbing as appropriate to insu...

Page 8: ...he two holes for mounting the L bracket to the wall The bracket should be located so that the 6 clamp assembly will be approximately 12 from the top of the contact column Drill a 1 2 hole at each of t...

Page 9: ...Base Flange Gasket Base Flange Nuts Washers 8ea Contact Column Exploded View Figure 4 4 Contact Column Installation Diagram Figure 4 3 6 Clamp Assembly Bolts nuts with bolt Nut washers 2ea Unistrut cu...

Page 10: ...AWG wire located at the bottom panel of the ozone generator see Appendix Section A can be interfaced to any control device i e pressure switch vacuum switch flow switch float switch ORP controller PPM...

Page 11: ...Preparation System Power 120VAC systems only plug the power cord into main power 240VAC systems only the power cord must be hard wired to the main power source Black L1 White L2 N and Green Ground No...

Page 12: ...y Step 3 Mount indicator cartridge on a suitable flat surface using the Clic mounting clamps provided Notes The indicator cartridge must be mounted vertically The indicator cartridge does not have a d...

Page 13: ...vertical position and the drain holes are below the level of the ozone generators ozone outlet fitting One clamp should be located so it fits around the Riser Tube Elbow and the other so it fits aroun...

Page 14: ...the injector manifold until the needle moves into the green zone If the needle is in the red zone on the vacuum in Hg side of the gauge gradually open the ball valve on the injector manifold until the...

Page 15: ...e it will open causing a loss of vacuum A loss of vacuum means ozone cannot flow from the vacuum break which in turn can cause an ozone leak Note If the vacuum break must be refilled with water discon...

Page 16: ...ary by following the steps outlined in the Start Up Calibration section Ozone Generator Indicator Lights Check the Main Power indicator light at the bottom of the ozone generator and Ozone LED s at th...

Page 17: ...one output LED will illuminate when ozone drive is being generated The LED will also pulse as the output increases or decreases with either the Manual Ozone Output Control located on the bottom of the...

Page 18: ...and or operating conditions in the equipment area will dictate the required frequency of this procedure Ozone Generators Cooling Fan Filters Clean or replace the cooling fan filter elements as requir...

Page 19: ...ielectric approximately 1 2 from either end of the glass making sure it is rolled squarely Step 6 Slide the dielectric into the heat sink cathode assembly Seat the dielectric into the O rings of the n...

Page 20: ...normal for some water to be flowing from the injector during this procedure Contact Vessel Cleaning Contact Column only Inspect the diffuser slots at the top of the contact column riser tube If they...

Page 21: ...place compressor or pink or white ATF module as required Replace indicating desiccant Unit is making excessive noise Unit not properly secured to floor Place unit on a flat level surface Shipping dama...

Page 22: ...ing Fault LED The Ozone Output LED s The remote 4 20mA control signal is not Check for loose wires or connections not responding to the remote sensed by the 4 20mA control board 4 20mA control signal...

Page 23: ...libration Debris on seat of vacuum break flapper valve Clean seat of flapper See Maintenance Procedures Annual Low vacuum Hydraulics Pneumatics out of adjustment See Start Up Calibration Steps 1 4 Def...

Page 24: ...ns Shown ClearWater Tech OXS90 Air Prep System with Cover Shown ClearWater Tech OXS90 Air Prep System with out Cover AIR PREP SYSTEM SPECIFICATIONS OXYGEN OUTPUT SCFH OXS90 Workhorse 12c 15 5 h x 17 w...

Page 25: ...Drive Board and Drive Transformer under board Reaction Chamber Power Supply Inline Particulate Filter 4 20mA Control Board Pressure Switch Cover Safety Switch External Loop Remote 4 20mA Control Lead...

Page 26: ...rs Drive Board and Drive Transformer XFMR under boards Inline Particulate Filter Power Supply Pressure Switch 4 20mA Control Board Cover Safety Switch External Loop Remote 4 20mA Control Leads Air Pre...

Page 27: ...00P RCC10 Dielectric Anode 2 RCC71 Non High Voltage End Cap Contact Dealer High Voltage End Cap Contact Dealer O ring Set ORS40 Drive Module Complete CD2000P DRM60 Drive Module Transformer HVT275 Driv...

Page 28: ...1 Filter Inline particulate filter FUS20 2 Fuse Bussmann MDL 5 5 amp 250VAC Slow Blow Main Power ORG110 4 O ring 2 CD reaction chamber pressurized end cap large ORG120 4 O ring 2 CD reaction chamber p...

Page 29: ...try Module With Fuses High Voltage Transformer Drive Board Remote 4 20mA Ozone Output Control Orange Purple Manual Ozone Output Control Fan Power Supply Cover Safety Switch Power Supply 4 20mA Control...

Page 30: ...afety Switch Power Supply Power Supply Fan Fan 24VDC 24VDC 24VDC 24VDC Manual Ozone Output Control Remote 4 20mA Ozone Output Control Orange Purple External Loop 4 20mA Control Board Variable Output S...

Page 31: ...30 Drive Module Input Voltages Shown Dual HO Drive Module APPENDIX Section E...

Page 32: ...nced with the product and or part must be clearly described The RGA number must appear prominently on the exterior of the shipped box es The product and or part must be packaged either in its original...

Reviews: