FieldSmart
®
Fiber Active Cabinet (FAC) 400
Installation Manual
_________________________________________________________
Proprietary Information: Not for use or disclosure except by written agreement with Clearfield.
108
Installing a Generator Connector
A generator connector (Gen Conn) allows you to connect an external power generator to the cabinet to sustain services
during an AC power outage. The cabinet supports a 30 Amp generator connector option, which you can install in the field.
Note:
This procedure is service-affecting for cabinets in service.
DANGER!
High voltage may be present. Only a qualified electrician should perform this task. Follow NEC and
local codes when handling power systems. Do not restore AC power until the task is complete.
At the local power transfer switch, disconnect AC power to the cabinet.
Open the cabinet’s front compartment door.
Install a circuit breaker for the Gen Conn circuit into the load center as follows:
a.
Remove the front panel from the AC load center.
b.
At the AC load center, switch the Gen Conn (if present) and Main circuit breakers to OFF.
c.
Install the Gen Conn circuit breaker:
• Get the Gen Conn breaker from the shipping package.
• Set the switch to OFF.
• Insert the breaker to the right of the Main breaker.
Prepare the battery base compartment for mounting a Gen Conn:
a.
Remove the battery base door. See Operating Cabinet Doors for instructions.
b.
Remove equipment from the battery base to gain access to the connector mounting location, as needed:
• If batteries are present, remove the batteries. See Replacing Batteries for instructions.
• (Optional) Remove the battery tray.
c.
Remove the blank plate that covers the generator connector mounting location. From inside the battery
compartment, remove the nuts from the four studs anchoring the blank plate to the compartment wall.
Note:
Do not discard the four mounting nuts. The nuts will be reused to install the generator connector.
d.
Pull the blank plate away from the wall to expose the connector mounting location.
Step 1:
Step 2:
Step 3:
Step 4:
To prepare for generator connector installation