FieldSmart
®
Fiber Active Cabinet (FAC) 400
Installation Manual
_________________________________________________________
Proprietary Information: Not for use or disclosure except by written agreement with Clearfield.
136
Specifications
Specifications for the Clearfield FAC 400 cabinet follow:
Dimensions
Local power configuration
(with 60 Ah battery base)
48” H x 19.7” W* x 24” D
* The 60 Ah battery compartment is 1.7” wider than the cabinet
Weight
Local power configuration
(with 60 Ah battery base)
222 lbs
Enclosure Mounting
Concrete pad
Clearfield cast-in-place template or pre-cast pad option
Pole
Clearfield pole-mounting kit option
Foundation vault
Third-party supplied
Equipment Mounting
Equipment mounting space
7 inches (4 RU)
Rack attributes
19-inch EIA standard; oriented for vertical mounting
Environmental
Heat exchanger
Door mounted, 300 Watt
External fan operation:
Fans turn on at 30C (1500 RPM)
Fan speed increases 40C to 55C (linear ramp from 1500 RPM to 3000 RPM)
Fan speed max at 55C and above (3000 RPM)
High temp alarm at 75C
Cooling capacity
20 Watts/°C
Thermal operating range
-40C to +46C
Environmental alarming
Environmental and intrusion alarms
Electrical (Local Power)
AC power system
220-240 VAC load center
Duplex convenience outlet (GFCI protected)
Generator connector (option)
30 Amp NEMA twist-lock (Hubbell)
DC power system
Two 25 Amp rectifier modules, autosenses and adjusts for low and high AC input
Battery backup
Support for (1) 60 Ah string of front post VRLA batteries (up to (2) 60 Ah strings with optional riser compartment);
battery heater and seismic protection options available
Cable Entrance
Outside plant entry
(2) 2.5-inch diameter entry ports
AC service entry (local power only)
(1) 1-inch diameter entry port
Compliance
Safety
UL 67
EMC
FCC Part 15, Class A
Telcordia
GR-487-CORE, Issue 2