43
FieldSmart
®
Fiber Active Cabinet (FAC) 400
__________________________________________________________
Installation Manual
Direct: 763.476.6866 • National: 800.422.2537 • www.SeeClearfield.com • techsupport@clfd.net
Manual 020419 REV A - Feb 2019
Installing a Wall-Mount Kit: Local Power with 60 Ah Battery Base(s)
A sturdy, plumb wall or H-frame can provide an effective mounting structure for elevating the cabinet above the ground,
particularly in areas subject to severe surface conditions such as flooding, mud, or heavy snow. Wall mounting also allows
cabinets to be installed in locations where the required terrestrial right-of-way may be unavailable.
Use the Clearfield wall-mount kit to provide the mounting fixture. The wall-mount kit consists of a support frame that at
-
taches directly to the wall or H-frame, including a base platform that provides exact entry locations for the cable conduits.
You can install the mounting kit onto an existing wall, or you can construct an H-frame at the installation site to support
the cabinet. Installing the wall-mount kit requires trenching cable conduit to the site and installing the mounting fixture on
the wall or H-frame.
FAC 400 wall-mount kits are available for local power cabinet configurations with a single or dual 60 Ah battery base.
Wall/H-Frame Mounting Guidelines
When installing the wall-mount kit, observe the following guidelines. Refer to the wall-mount drawings for guidance.
Guidelines
Follow these guidelines to ensure proper mounting support for the cabinet. Adjust for local conditions or practices
as required.
• The pole/post must be vertically plumb.
•
The pole/post must support a minimum load weight, as required for the cabinet configuration:
Note:
These weights include a fully loaded cabinet.
• Single 60 Ah battery base
: 450 lbs
• Dual 60 Ah battery base
: 680 lbs
• The top of the base platform must be a minimum of 18 inches above the ground for both single and dual 60 Ah battery
base configurations.
•
The wall or H-frame must stand a minimum height above the ground, as required for the cabinet configuration:
• Single 60 Ah battery base:
The wall or H-frame must stand at least 75 inches above ground.
• Dual 60 Ah battery base:
The wall or H-frame must stand at least 86 inches above ground.
Note:
The minimum heights assume a distance of 18 inches above the ground to the top of the base platform. To
elevate the cabinet higher than 18 inches above ground, use a wall or H-frame with sufficient additional height.